T
ROUBLESHOOTING (continued)
PAGE 56
_____________________________________________________________________________________________________________________________________________________________________________________
This section of the manual is designed to help you to isolate and correct problems that may occur
during the operation of your TARM EXCEL BOILER.
SYMPTOM:
POSSIBLE CAUSE:
REMEDY:
NO HEAT IN HOUSE
Boiler Temperature is below
150
°
F while burning wood
No Fuel in Boiler
Low Fan Output
Restart or re-light fire
Fan wheel dirty—CLEAN
Air Ducts Plugged -- CLEAN
Fan does not operate
Check power and control panel
components with multi-meter
By-pass damper is open, not sealing
Close by-pass damper, CLEAN
Combustion chamber is obstructed
Clear ash and other obstructions
through lower door
Boiler is dirty
Clean ash off refractory
Clear Ash from floor of boiler
Brush Heat Exchange Tubes
Wood is un-split or unseasoned
Split wood and season to 20%
moisture or less
Fan operates slowly
Bad motor capacitor-replace
Boiler Temperature is below
140
°
F, wood fan doesn’t shut off
Boiler did not get up to operating
temperature before dropping below
140
°
F
All of above possible
Be sure to fire boiler so it heats
to above 175
°
F (80
°
C) after a
cold start
Creosote in Chimney
By-pass damper not fully closed:
smoke by-passing combustion
chamber
Check by-pass assembly- adjust
or clean as necessary
A blockage in primary air ducts or
openings
Clean
Smoke smell around boiler after
combustion fan shuts off
Down draft in chimney causing boiler
to burn backwards thru primary air
ducts & draft fan
Consult a chimney professional
or Tarm USA, Inc
Leaky Door Gaskets
Replace as necessary
Wood Combustion Fan shuts off
after 15 minutes
Desired Flue Temperature not
reached
Lower Flue Temperature Sensor
Use drier or smaller wood when
starting your fire
Boiler Temperature is below
140
°
F while burning oil or gas.
Out of fuel
Check oil or gas supply
Excessive heat demand
Have serviceman check nozzle
size and BTU input of burner –
increase within specifications
Boiler Temperature above 150
°
F
Air in piping
Call Serviceman
Circulator not operating
Call Serviceman
Not enough radiation in house
Add radiation as needed
Boiler functions well with good
burn times but inadequate on
coldest days
Boiler temperature is set too low
Increase boiler water
temperature by adjusting the “HI”
setting on the L8124 Control to
190
°
F
Excessive heat dumped into
over heat zone
Overheat control set too low
Increase “low” setting on L8124C
to 210
°
F
56
Summary of Contents for 2000
Page 1: ......
Page 4: ......
Page 8: ... Intentionally left blank PAGE 4 4 ...
Page 13: ...FEATURES AND SPECIFICATIONS PAGE 9 9 ...
Page 28: ...FIELD WIRING DIAGRAMS PAGE 24 ...
Page 29: ...24 WIRING SCHEMATIC FOR CONTROLS PAGE 25 ...
Page 30: ...This is an insert page 25 ...
Page 63: ...TARM EXCEL CAUTION LABEL PAGE 58 58 ...
Page 65: ...BOILER Parts List PAGE 60 60 ...
Page 66: ...BOILER Parts List PAGE 61 61 ...