2. BRAZING
DANGER
1. Refrigerant R-404A itself is not flammable at atmospheric pressure and
temperatures up to 176
° F.
2. Refrigerant R-404A itself is not explosive or poisonous. However, when
exposed to high temperatures (open flames) R-404A can be decom-
posed to form hydrofluoric acid and carbonyl fluoride both of which are
hazardous.
3. Always recover the refrigerant and store it in an approved container. Do
not discharge the refrigerant into the atmosphere.
4. Do not use silver alloy or copper alloy containing Arsenic.
5. Do not use R-404A as a mixture with pressurized air for leak testing.
Refrigerant leaks can be detected by charging the unit with a little refrig-
erant, raising the pressure with nitrogen and using an electronic leak
detector.
Note: All brazing-connections inside the bin are clear-paint coated. Sandpaper the
brazing connections before unbrazing the components. Use a good abrasive cloth
to remove coating.
Summary of Contents for F-2000MLH
Page 13: ...13 2 CONDENSER UNIT URC 20F...
Page 15: ...15 II GENERAL INFORMATION 1 CONSTRUCTION F 2000MWH C...
Page 16: ...16 F 2000MRH C F 2000MRH3 C...
Page 17: ...17 F 2000MLH C...
Page 19: ...19 F 2000MRH3 C...
Page 20: ...20 F 2000MLH C...
Page 21: ...21 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERATION CIRCUIT F 2000MWH C...
Page 22: ...22 F 2000MRH C F 2000MRH3 C...
Page 23: ...23 F 2000MLH C...
Page 24: ...24 2 WIRING DIAGRAMS F 2000MWH C...
Page 25: ...25 F 2000MRH C...
Page 26: ...26 F 2000MRH3 C...
Page 27: ...27 F 2000MLH C...
Page 29: ...29 b When Reservoir has been filled Gear Motor starts immediately...
Page 32: ...32 e Low Water Except Water cooled Model where Compressor will operate intermittently...
Page 38: ...38...
Page 68: ...68...