55
2. LOW ICE PRODUCTION
PROBLEM
POSSIBLE CAUSE
REMEDY
[1] Low ice production
a) Refrigerant Line
1. Gas leaks.
1. See "1. [5] a) Refrigerant
Line."
2. Refrigerant line
clogged.
2. Replace the clogged
component.
3. Overcharged. [Except
F-2000MLH/-C]
3. Recharge.
b)
1. Dirty Air Filter or
Condenser. [Except
F-2000MLH/-C]
1. Clean.
2. Ambient or condenser
water temperature too
warm. [Except
F-2000MLH/-C]
2. Get cooler.
3. Condenser water
pressure too low or
off. [Water-cooled
model only]
3. Check and get
recommended pressure.
4. Fan rotating too slow. 4. See "3 [1] a) Fan Motor."
5. Water Regulating
Valve clogged. [Water-
cooled model only]
5. Clean.
6. Condensing unit out of
order. [F-2000MLH/-C
only]
6. Check condensing unit.
c) Expansion Valve (not
adjustable)
1. Low-side pressure too
low.
1. Replace.
2. Low-side pressure too
high.
2. See if Expansion Valve
Bulb is mounted properly,
and replace the valve if
necessary.
d) Evaporator Pressure
Regulator
[F-2000MLH/-C only]
1. Evaporator Pressure
Regulator set too high
or too low.
1. Check Evaporator
Pressure Regulator, and
adjust or replace it if
necessary.
High-side Pressure Too
High
Summary of Contents for F-2000MLH
Page 13: ...13 2 CONDENSER UNIT URC 20F...
Page 15: ...15 II GENERAL INFORMATION 1 CONSTRUCTION F 2000MWH C...
Page 16: ...16 F 2000MRH C F 2000MRH3 C...
Page 17: ...17 F 2000MLH C...
Page 19: ...19 F 2000MRH3 C...
Page 20: ...20 F 2000MLH C...
Page 21: ...21 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERATION CIRCUIT F 2000MWH C...
Page 22: ...22 F 2000MRH C F 2000MRH3 C...
Page 23: ...23 F 2000MLH C...
Page 24: ...24 2 WIRING DIAGRAMS F 2000MWH C...
Page 25: ...25 F 2000MRH C...
Page 26: ...26 F 2000MRH3 C...
Page 27: ...27 F 2000MLH C...
Page 29: ...29 b When Reservoir has been filled Gear Motor starts immediately...
Page 32: ...32 e Low Water Except Water cooled Model where Compressor will operate intermittently...
Page 38: ...38...
Page 68: ...68...