MAN0974-14-EN_XL7_XL7P_UM
July 6, 2022
Page 165 | 199
4.
Once the cloning is successful, OCS gives a message as below:
Figure 18.5
–
Cloning Status
Make/Create clone can also be triggered by setting %SR164.9 bit to “1” from Ladder program or graphics.
Once the operation is completed, this bit is made zero by the firmware. When Make clone operation is
triggered by this SR bit, it does not ask the user for confirmation for making clone. The success / failure of
the operation is also not notified on screen to the user.
In case of
failure of “Make Clone” operation, %SR164.11 bit is set to “1” by the firmware and never reset.
NOTE
: Backup of registers in flash memory is not performed by Clone Feature. If user desires, Backup
should be done as explained in the