Electrolyte Circulation System
7145240031 V1.1 (01.2013)
System overview
The pump- and control unit comes with a plastic housing for wall mounting. The air outlet of this unit is con-
nected to the air tubing (refer to Figure 2). For switching the air pump during battery charge periods an inductive
current sensor is connected to the pump- and control unit. The power supply for the pump- and control unit
comes from the battery (24V / 48V). Refer also to Figure 3 and Figure 4.
Note: For 48V battery systems with larger cells (18 OPzS solar.power 3250 up to 26 OPzS solar.power 4700)
two electrolyte circulation pumps are required (refer to Figure 5).
Figure 3: Schematic diagram
Figure 2: Pump and control unit