Technical characteristics
Battery
Applicable Type
OPzS solar.power
Capacity Range at C100
6 OPzS solar.power 910Ah to
26 OPzS solar.power 4700Ah
Pump
Motor
Brushless
Volumetric current
720 l/h at 100 mbar
Voltage / Current 24V DC / 48V DC (ca. 0.6A / 0.3A)
Power consumption Ca. 15W during operation / ca. 0.6W in standby
(approx. 20 Wh during 6h battery charging phase)
Housing (Pump and Control Unit)
Figure 30: Dimensions of pump- and control unit