Setpoint Profiler
Video Recorder – User Manual
193
Table 5-5 Edit Profile Prompts
Prompt
Range/Selections
Definition
RAMP TYPE
VAL/DUR, TIME, RATE,
EXTERNAL
See
4 types of ramp segments
on page 178.
TIME UNITS
SECS, MINS, HOURS
Select the time units to be used by all segments
of the profile.
EDIT SEGMENTS
See Table 5-6.
GUAR SOAK LO LIM
OFF or number
The profiler will Hold if PV #1 or PV #2 deviates
more than this much below the profiler output.
See
Guaranteed Soak
on page 182 for details.
GUAR SOAK HI LIM
OFF or number
The profiler will Hold if PV #1 or PV #2 deviates
more than this much above the profiler output.
See
Guaranteed Soak
on page 182 for details.
HYSTERESIS
OFF or number
See
Hysteresis
on page 182 for details.
BATCH FIRST
SEGMENT
0-63
Specify the first segment of the batch phase.
Prior segments are the start-up phase. A value
of 0 indicates a single phase profile. See
Two
types of profiles
on page 177 for details.
BATCH LAST
SEGMENT
0-63
Specify the last segment of the batch phase.
Segments after this segment are the shutdown
phase. A value of 0 indicates a single phase
profile. See
Two types of profiles
on page 177
for details.
(continued)
Summary of Contents for VRX180
Page 1: ...Issue 3 03 03 US1I 6228 Video Recorder VRX180 User Manual ...
Page 2: ...Issue 3 03 03 US1I 6228 ...
Page 6: ...iv Video Recorder User Manual ...
Page 48: ...Installation Video Recorder User Manual 34 ...
Page 222: ...Setpoint Profiler Video Recorder User Manual 208 ...
Page 234: ...Online Operations Using Primary Displays Video Recorder User Manual 220 ...
Page 278: ...Appendix A Video Recorder User Manual 264 ...