Page 66
ST 700 Series HART/DE Option User’s Manual
Revision 4.0
2.
Click the
Calibration
button to display the
CALIBRATION
menu.
3.
In the
Apply Values
group, click
Set LRV
. The following message will be displayed;
a.
The value of the input shown in the Set LRV box above updates only when the popup
is called up.
b.
To update the input value, click
No
, and then click the
Set LRV
button in the
CALIBRATION
display.
4.
Set the LRV as follows:
a.
While observing the PV value at the physical process element (using a sight glass, for
example), adjust it to the desired minimum (0 %) level, and then click
Set LRV.
b.
If the displayed value is satisfactory, click
Yes
to copy the Input Value to the LRV in
the Transmitter. If not, click
NO
and repeat this step.