Revision 4.0
ST 700 Series HA
RT/DE Option User’s Manual
Page 59
7.5.3 Input Calibration Procedure
7.5.3.1 Correct the Input at Zero
1.
Start the
MC Toolkit
application. Establish communication between the Transmitter and the
MC Toolkit.
2.
From the DE MAIN MENU, click
Configure
to open the
DE CONFIGURE
display.
3.
From the
DE CONFIGURE
display:
a.
Use the
PV Units
drop-down list to click the appropriate engineering units.
b.
Use the keyboard to enter the desired
LRV
and
URV
values.
c.
Click the
Send
button to copy the newly entered values to the Transmitter. When the
copy operation is complete,
Send
will be displayed in half-intensity.
4.
Click the
Back
button to go to the
DE MAIN MENU
; then click the
Calibration
button. The
CALIBRATION
box will be displayed.
5.
Click the
Back
button to go to the
DE MAIN MENU
; then click the
Calibration
button. The
CALIBRATION
box will be displayed.