Revision 4.0
ST 700 Series HA
RT/DE Option User’s Manual
Page 135
Online/Device
Setup/Calibration
PV Levels
Displays a graphic representation of all PV ranges
and limits for the ST 700 Pressure Transmitter
Calibration Methods
The following calibration methods are available:
Apply Values:
Performs a Set LRV and/or
Set URV to configure the LRV/URV to
applied inputs.
Enter Values:
Enter desired LRV and URV
value to configure the desired operating
range. Valid entries are from LTL to UTL
(lower/upper transducer limits).
D/A Trim:
Perform an analog output
calibration at 4.00 and 20.00mA (0% and
100% output).
Zero Trim:
Perform an input calibration
correction by applying process input at zero.
LRV Correct:
Perform an input calibration
correction by applying process input at the
configured LRV level.
URV Correct:
Perform an input calibration
correction by applying process input at the
configured URV level.
Reset Corrects:
Clear all user calibration
adjustments.
Filter Performance
Selection
Configure the desired performance for the Output
Speed of Response Filter. Select from:
Standard SOR :
Excellent speed of
response to input changes with optimal
noise performance
Fast SOR:
Fastest speed of response to
input changes
Correct URV
Records
Displays the time and date history records for the
last three URV Correct calibrations.
Correct LRV
Records
Displays the time and date history records for the
last three LRV Correct calibrations.
Zero Trim Records
Displays the time and date history records for the
last three Zero Trim calibrations.
Reset Correct
Records
Displays the time and date history records for the
last three times Reset Corrects was issued.