Experion communicates the channel mode status to
the corresponding ST 700 transmitters. Upon
receiving this status, if the value is
MAN
, the
transmitter displays an
M
and
Available for
Maintenance
on the local display of the transmitter.
The status display on the transmitter ensures that the
field technician can locate and perform the
maintenance work on the correct transmitter without
impacting the integrated devices in the process loop.
The transmitter continues to display the
Available for
Maintenance
status on its local display until the
PV
Source
status of the corresponding AI channel is
changed to
AUTO
/
SUB
or the transmitter is power
cycled.
For more information, refer to the Experion
Knowledge Builder
Online/Device
Setup/Basic Setup/
Device Information
(
Continued …)
Device ID
Displays the HART unique long address of the ST 700
Pressure Transmitter
Final Asmbly num
Displays the final assembly number of the ST 700
Pressure Transmitter
Universal rev
Displays the HART Universal Revision of the ST 700
Pressure Transmitter
Fld dev rev
Displays Field Device Revision of the ST 700
Pressure Transmitter
Software rev
Displays the Electronics Board Software Revision of
the ST 700 Pressure Transmitter
Loop mA
Click the Loop Current Mode configuration:
Enable
: enables loop current mode (analog
output will operate as a 4 to 20mA signal
consistent with the transmitter output)
Disable
: disables loop current mode (analog
output will be fixed at 4mA)
PV Units
Click one of the pre-programmed engineering units.
ST 700 Transmitters with inches of water ranges are
factory calibrated using pressure referenced to 39.2
o
F
(4
o
C). Pressure readings can be displayed in the
following engineering units:
inH
2
O
inHg
ftH
2
O
mmH
2
O
mmHg
psi
bar
mbar
g/cm
2
kg/cm
2
Pa
kPa
torr
atm
MPa
inH
2
O @ 4
o
C
mmH
2
O@4
o
C
inH
2
O @
60
o
F