Control Panel Installation
151430
4-37
4.13.3.2 Installing 2-Wire Class A Smoke Detector
To install a Class A two-wire smoke detector, wire as shown in Figure 4-37.
Figure 4-37 Two-Wire Class A Smoke Detector Connections
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-37 uses both Flexput circuit 5 and 6, so in programming it
would be referred to as point 5.
Note:
Flexput circuit 5 and 6
used as an example.
Any Flexput point pairing
could be used.
Supervised
Power Limited
Maximum Impedance per
Circuit is 50
Ω
firealarmresources.com