Control Panel Installation
151430
4-13
4.6
RA-2000 Remote Annunciator Installation
The optional Model RA-2000 Remote Annunciator, shown in Figure 4-11, performs the same
functions as the on-board annunciator. Operation is identical. The RA-2000 can be surface or
flush mounted.
Figure 4-11 Model RA-2000 Remote Annunciator, Front View
RA-2000 installation involves the following steps:
1. Make sure power is off at the panel.
2. Mount the RA-2000 in the desired location (see Section 4.6.1).
3. Connect the RA-2000 to the panel (see Section 4.4).
4. Use the DIP switches on the back of the RA-2000 to assign an SBUS ID# to the RA-2000
5. The RA-2000 module must be added to the system through programming. JumpStart
AutoProgramming will add the module automatically (see Section 8.1.3). You can also
add it manually (see Section 9.2.2). Select a name, if desired (see Section 9.2.1.1).
firealarmresources.com
Summary of Contents for Silent Knight IFP-2000 Module 3
Page 2: ...firealarmresources com ...
Page 12: ...IFP 2000 Installation Manual viii firealarmresources com ...
Page 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...
Page 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...
Page 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...
Page 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...
Page 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...
Page 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...
Page 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...
Page 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...
Page 236: ...firealarmresources com ...
Page 237: ...firealarmresources com ...