IFP-2000 Installation Manual
3-12
151430
JumpStart AutoProgramming automatically selects some options for SLC devices (see “JumpStart
AutoProgramming” section of this chart). You can change options selected by JumpStart
AutoProgramming, if necessary and further customize input point options.
U
Program type of switch (manual pull, fire drill, and so on), if necessary.
(JumpStart AutoProgramming assigns all switches as Manual Pull type.)
U
If the installation includes duct detectors, program detector type.
(JumpStart AutoProgramming does not distinguish duct detectors from
ordinary smoke detectors.)
U
Assign a name (or description) to the point.
U
Assign input points to zones, if necessary. (JumpStart AutoProgramming
assigns all input points to Zone 1.)
Zone Configuration
U
Add the zone to the system if it does not already exist.
U
Program a name (or description) for the zone.
U
Select alarm delay options (detection characteristics) for zone.
U
Select heat detector trip temperature and/or smoke sensitivity level for
photoelectric smoke detectors. (JumpStart AutoProgramming selects 150°F
for heat detectors and Low sensitivity for smoke detectors.)
Output Point Configuration
Conventional notification circuits (circuits 1-8):
U
Enable circuits used for notification appliances through programming, if
necessary.
Conventional relay circuits (circuits 9-10):
U
Select options for relay circuits, if desired. Note: Relay circuits will always
output continuously (constant pattern), even if assigned to an Output Group
that uses a different output pattern.
Auxiliary power circuits (circuits 1-8):
U
Enable any circuit used for auxiliary power devices through programming.
U
Select type of power (door holder, constant, or resettable)
Addressable relay modules
U
Assign addressable relay modules to output groups through programming.
(JumpStart AutoProgramming assigns all relay modules to Group 1.)
LED output points (from the 5880 LED I/O module or 5865/66 LED Annunciator)
U
Assign LED modules to output groups through programming.
All output circuits (1-8):
U
Disable (set to UNUSED) any unused circuits. If you do not disable unused
output circuits, they will cause a trouble condition (unless an EOL resistor
is used).
U
Select a name for the point, if desired.
Output Group Configuration
U
Add the group to the system if it does not already exist.
U
Assign output points to the group.
U
Program a name (or description) for the group, if desired.
Select “group properties” (see below).
U
Select options for activation with system switches.
Task
See Sec.
(for more info.)
firealarmresources.com
Summary of Contents for Silent Knight IFP-2000 Module 3
Page 2: ...firealarmresources com ...
Page 12: ...IFP 2000 Installation Manual viii firealarmresources com ...
Page 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...
Page 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...
Page 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...
Page 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...
Page 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...
Page 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...
Page 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...
Page 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...
Page 236: ...firealarmresources com ...
Page 237: ...firealarmresources com ...