Reporting
151430
11-3
Detector trouble
FT
Zone #
FTNN000ZZZ
1
373
00
Zone #
Detector trouble restore
FJ
Zone #
FJNN000ZZZ
3
373
00
Zone #
External Reset/Silence/Fire Drill switch trouble
UT
Zone #
UTNN000ZZZ
1
373
00
000
External Reset/Silence/Fire Drill switch trouble restore
UJ
Zone #
UJNN000ZZZ
3
373
00
000
Manual pull switch alarm
FA
Zone #
FANN000ZZZ
1
115
00
Zone #
Manual pull switch alarm restore
FH
Zone #
FHNN000ZZZ
3
115
00
Zone #
Manual pull switch trouble
FT
Zone #
FTNN000ZZZ
1
373
00
Zone #
Manual pull switch trouble restore
FJ
Zone #
FJNN000ZZZ
3
373
00
Zone #
Notification output trouble
FT
Zone #
FTNN000ZZZ
1
320
00
Group #
Notification output trouble restore
FJ
Zone #
FJNN000ZZZ
3
320
00
Group #
Positive Alarm Sequence acknowledge switch trouble
FT
Zone #
FTNN000ZZZ
1
373
00
Zone #
Positive Alarm Sequence acknowledge switch trouble restore
FJ
Zone #
FJNN000ZZZ
3
373
00
Zone #
SLC LED Module trouble
ET
Zone #
ETNN000ZZZ
1
333
00
000
SLC LED Module trouble restore
ER
Zone #
ERNN000ZZZ
3
333
00
000
Supervisory/Tamper alarm condition
SS
Zone #
SSNN000ZZZ
1
203
00
Zone #
Supervisory/Tamper alarm condition restore
SR
Zone #
SRNN000ZZZ
3
203
00
Zone #
Supervisory/Tamper switch trouble
ST
Zone #
STNN000ZZZ
1
373
00
Zone #
Supervisory/Tamper switch trouble restore
SJ
Zone #
SJNN000ZZZ
3
373
00
Zone #
System-based AUX1 switch alarm
UA
Zone #
UANN000ZZZ
1
140
01
000
System-based AUX1 switch alarm restore
UH
Zone #
UHNN000ZZZ
3
140
01
000
System-based AUX1 switch trouble
UT
Zone #
UTNN000ZZZ
1
373
01
000
System-based AUX1 switch trouble restore
UJ
Zone #
UJNN000ZZZ
3
373
01
000
System-based AUX2 switch alarm
UA
Zone #
UANN000ZZZ
1
140
02
000
System-based AUX2 switch alarm restore
UH
Zone #
UHNN000ZZZ
3
140
02
000
System-based AUX2 switch trouble
UT
Zone #
UTNN000ZZZ
1
373
02
000
System-based AUX2 switch trouble restore
UJ
Zone #
UJNN000ZZZ
3
373
02
000
Water flow switch alarm
SA
Zone #
SANN000ZZZ
1
113
00
Zone #
Water flow switch alarm restore
SH
Zone #
SHNN000ZZZ
3
113
00
Zone #
Water flow switch trouble
ST
Zone #
STNN000ZZZ
1
373
00
Zone #
Water flow switch trouble restore
SJ
Zone #
SJNN000ZZZ
3
373
00
Zone #
Zone-based acknowledge switch trouble
FT
Zone #
FTNN000ZZZ
1
373
02
Zone #
Zone-based acknowledge switch trouble restore
FJ
Zone #
FJNN000ZZZ
3
373
02
Zone #
Zone-based AUX1 switch alarm
UA
Zone #
UANN000ZZZ
1
140
01
Zone #
Zone-based AUX1 switch alarm restore
UH
Zone #
UHNN000ZZZ
3
140
01
Zone #
Zone-based AUX1 switch trouble
UT
Zone #
UTNN000ZZZ
1
373
01
Zone #
Zone-based AUX1 switch trouble restore
UJ
Zone #
UJNN000ZZZ
3
373
01
Zone #
Zone-based AUX2 switch alarm
UA
Zone #
UANN000ZZZ
1
140
02
Zone #
Zone-based AUX2 switch alarm restore
UH
Zone #
UHNN000ZZZ
3
140
02
Zone #
Zone-based AUX2 switch trouble
UT
Zone #
UTNN000ZZZ
1
373
02
Zone #
Zone-based AUX2 switch trouble restore
UJ
Zone #
UJNN000ZZZ
3
373
02
Zone #
Point Events
Note:
For IDP devices, sensors 1–159 are reported as Points 1–159, modules 1–159 are reported as Points 201–359.
An unexpected SLC device has been detected
pi Exp. ID
XE
Point #
XENNXXPPPP
1
380
Exp. ID
Point #
An unexpected SLC device has been removed
pi Exp. ID
XI
Point #
XINNXXPPPP
3
380
Exp. ID
Point #
Auxiliary power disabled
pi Exp. ID
FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Auxiliary power enabled
pi Exp. ID
FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Auxiliary power Trouble
pi Exp. ID
FT
Point #
FTNNXXPPPP
1
320
Exp. ID
Point #
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier (same as IFP-1000 Rev 9)
SIA IFP-2000
Event Description
Module ID #
(If Any)
SIA Event
Codes
Parameter
Fixed Length Format
NN - panel ID
XX - SBUS ID
ZZZ - zone #
PPPP - Point #
AAAAAA-account #
Qualifier
Event
Code
Group #
Contact #
firealarmresources.com
Summary of Contents for Silent Knight IFP-2000 Module 3
Page 2: ...firealarmresources com ...
Page 12: ...IFP 2000 Installation Manual viii firealarmresources com ...
Page 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...
Page 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...
Page 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...
Page 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...
Page 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...
Page 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...
Page 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...
Page 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...
Page 236: ...firealarmresources com ...
Page 237: ...firealarmresources com ...