IFP-2000 Installation Manual
9-30
151430
9.6.5.2 Low AC Report Time
Note: You must select 1-3 hours in UL central station installations and UL remote signaling installations.
You can adjust the number of hours before a Low AC report will be sent to the central station.
To program low AC report delay, follow these steps:
Note: Steps continued from step 6 of Section 9.6.5.1.
Figure 9-12 Low AC Report Delay Programming Screen
6. Enter the number of hours before a low AC report will be sent to the central station, then
press
9.6.5.3 Automatic Daylight Savings Adjustment
The control panel has an automatic DST (Daylight Saving Time) adjustment feature. Before
January 2007, if this feature is enabled (set to
Yes
), the system clock will switch to DST on the
first Sunday in April at 2:00 a.m. and revert to standard time on the last Sunday in October at
2:00 a.m. After January 2007, if this feature is enabled, the system clock will start and end
DST according to the settings made in Misc. Options 3 (see Section 9.6.7.2). If this feature is
not enabled (set to
No
) the Daylight Saving Time change is not made to the system clock.
To enable or disable DST adjustment continue programming from step 6 above:
7. Select Y (enabled) or N (disabled) by pressing the
or
arrow, then press
.
9.6.5.4 Clock Display Format (AM/PM or Military)
To change the system clock display format, continue programming from step 7 above:
8. Select AMPM (for AM/PM display format) or MIL (for military or 24 hr display format)
by pressing the
or
arrow, then press
.
Low AC Report
Delay in Hours
(00-30)
firealarmresources.com
Summary of Contents for Silent Knight IFP-2000 Module 3
Page 2: ...firealarmresources com ...
Page 12: ...IFP 2000 Installation Manual viii firealarmresources com ...
Page 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...
Page 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...
Page 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...
Page 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...
Page 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...
Page 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...
Page 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...
Page 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...
Page 236: ...firealarmresources com ...
Page 237: ...firealarmresources com ...