IFP-2000 Installation Manual
1-4
151430
1.3
Compatible Products
Table 1-1 lists the products available from Silent Knight for use with the IFP-2000.
Table 1-2: IFP-2000 Compatible Products
Type of
Device
Model
Description
IDP
Addressable
SLC Devices
See Section 7.1 for a list of compatible devices.
Other
Modules
5815XL SLC Expander
Each 5815XL allows up to 159 IPD sensors and 159 IDP modules to be added to the system.
The number of 5815XLs that can be added to the system is limited only by the maximum
number of SBUS devices. However the maximum point count is limited to 636 per panel.
This allows the installer to distribute the 636 points on more than two SLC loops and also
allows all 636 points to be all sensors or all modules or any combination of sensors and
modules.
5824 Serial/Parallel Printer
Interface Module
Allows a printer to be attached for the on-site event logging.
Maximum of two 5824s per control panel
RPS-1000 Intelligent Power
Module
Provides additional power, six Flexput™ circuits, and two Form C relays. See
Model RPS-
1000 Installation Instructions P/N 151024
.
5496 Intelligent Power
Module
Provides four additional Notification Appliance Circuits/Auxiliary power.
RA-2000 Remote Fire Alarm
Annunciator
Same operation, similar appearance as on-board annunciator.
5865-3 and 5865-4 LED
Annunciator
LED annunciator can display up to 30 LEDs (15 red and 15 yellow). 5865-4 has key
switches for silence and reset, and a system trouble LED.
5880 LED I/O Module
Driver for up to 40 LEDs. Interfaces with customized annunciator boards. In addition the
5880 has eight generic switch input points.
5883 General Purpose Relay
Module
Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883s can be
used with each 5880 module.
VIP-VCM
Voice Control Module used with the IFP-2000VIP.
Refer to the
VIP-Series
Installation Manual
P/N
151286 for more
information on these
accessories. VIP series is
not FM approved for use
with IFP-2000
VIP-SW16
16 switch expander with the IFP-2000VIP.
VIP-50
50 watt audio amplifier
VIP-CE4
Provides four additional audio circuits for the VIP-50
VIP-RM2000
Remote Microphone used with the IFP-2000VIP.
Misc.
7860 Telephone Cord
RJ31X cord for connecting phone line to the IFP-2000.
Silent Knight Software Suite
(SKSS-2)
For communication and panel programming with a Windows-based computer and *modem
(not sold by Silent Knight, see Table 1-3 for compatible modems). Enables remote viewing
of detector status and event history.
RBB
Remote Battery Box for mounting backup batteries up to 35AH that are too large to fit into
the main control panel cabinet.
Dimensions: 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D)
AB-55
Remote Battery Box for mounting backup batteries up to 55AH that are too large to fit into
the main control panel cabinet.
Dimensions: 20" W x 12" H x 7.5" D (50.8 cm W x 30.48 cm H x 19.05 cm D)
firealarmresources.com
Summary of Contents for Silent Knight IFP-2000 Module 3
Page 2: ...firealarmresources com ...
Page 12: ...IFP 2000 Installation Manual viii firealarmresources com ...
Page 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...
Page 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...
Page 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...
Page 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...
Page 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...
Page 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...
Page 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...
Page 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...
Page 236: ...firealarmresources com ...
Page 237: ...firealarmresources com ...