IFP-2000 Installation Manual
9-20
151430
9.5.3
Point Programming For 5880, and 5865 Modules
To program 5880 or 5865 module points:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
Display reads:
Initializing
Please wait . . .
3. Press
to enter point menu.
4. Press the
or
arrows to select the desired module. Refer to Section 8.5 for available
choices.
5. Press .
Figure 9-7 Programming Points Screen for 5880 and 5865 Modules
6. Enter the point number.
7. Press .
8. Press the
or
arrows to select the type (Notification or unused).
9. Press .
10. Press the
or
arrows to select the desired Group.
11. Press .
12. Edit module name. See Section 9.5.3.1.
Or
7
4
firealarmresources.com
Summary of Contents for Silent Knight IFP-2000 Module 3
Page 2: ...firealarmresources com ...
Page 12: ...IFP 2000 Installation Manual viii firealarmresources com ...
Page 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...
Page 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...
Page 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...
Page 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...
Page 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...
Page 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...
Page 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...
Page 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...
Page 236: ...firealarmresources com ...
Page 237: ...firealarmresources com ...