IFP-2000 Installation Manual
9-32
151430
9.6.6
Miscellaneous Options 2
Through this programming option you can turn the strobe synchronization during silence
feature On or Off, and select the control panel to report events by zone or by point.
To edit miscellaneous options 2:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
Display reads:
Initializing
Please wait . . .
3. Select
for System Options.
4. Select
for Miscellaneous Options 2.
9.6.6.1 Strobes Active when Silenced
When “SYNC Strobe:” is Selected as Y (Yes) then strobes will continue to flash when the
system is silenced and will stop flashing when the system is reset.
Note: The “SYNC Strobe:” only functions with outputs that use a synchronized output pattern.
5. Press the
or
arrow to toggle this selection between Y (Yes) or N (No).
6. Press
or
to make your selection and move to the next programming option.
9.6.6.2 Auto Display Oldest Event
When this feature is programmed Y (Yes) then the oldest un-acknowledge event will
automatically display on the control panel and remote annunciators after there has been no
activity on any system touchpad for two minutes.
7. Press the
or
arrow to toggle this selection between Y (Yes) or N (No).
8. Press
or
to make your selection and move to the next programming option.
9.6.6.3 IFP-RPT Repeater Installed
When the “Repeater Installed” option is programmed Y (yes) then panel will supervise the
IFP-RPT Repeater. Set N (no) when an IFP-RPT Repeater is not installed.
9. Press the
or
arrow to toggle this selection between Y (Yes) or N (No).
10. Then press
or
.
7
5
5
firealarmresources.com
Summary of Contents for Silent Knight IFP-2000 Module 3
Page 2: ...firealarmresources com ...
Page 12: ...IFP 2000 Installation Manual viii firealarmresources com ...
Page 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...
Page 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...
Page 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...
Page 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...
Page 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...
Page 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...
Page 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...
Page 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...
Page 236: ...firealarmresources com ...
Page 237: ...firealarmresources com ...