Satellite XT 4-20 mA Versions
Alarm 1 Trigger
Used to define the trigger condition for Alarm 1
activation. Default setting is Greater Than. Use the
<set> key to enter. The instrument will show the actual
setting.
Greater Than
Defines that an Alarm 1 condition will be indicated when
the actual gas concentration exceeds the preset level
for Alarm 1.
Actuate the cursor keys <up> or <down> to change.
Actuate the <set> key to confirm or <esc> to exit.
Less Than
Defines that an Alarm 1 condition will be indicated when
the actual gas concentration falls below the preset level
for Alarm 1.
Actuate the cursor keys <up> or <down> to change.
Actuate the <set> key to confirm or <esc> to exit..
Alarm 1 Latch
Used to define the Alarm 1 activation to be either latch
-
ing or non-latching.
Default setting is enabled. Use the <set> key to enter.
The instrument will show the actual setting.
When latching is enabled, alarm reset must be done
manually. Nonlatching alarms will be reset automati-
cally, upon correction of the alarm condition.
Disabled
Defines the Alarm 1 activation to be non-latching.
Actuate the cursor keys <up> or <down> to change.
Actuate the <set> key to confirm or <esc> to exit.
Enabled
Defines the Alarm 1 activation to be latching.
Actuate the cursor keys <up> or <down> to change.
Actuate the <set> key to confirm or <esc> to exit.
s e l e c t :
3
o f
4
A L A R M 1
A L ARM 1 T R I GGER
s e l e c t :
1
o f
2
A L A R M 1 T R I G G E R
GRE A T ER T HAN
s e l e c t :
2
o f
2
A L A R M 1 T R I G G E R
L E S S T HAN
s e l e c t :
1
o f
2
A L A R M 1 L A T C H
D I S A B L ED
s e l e c t :
2
o f
2
A L A R M 1 L A T C H
ENA B L ED
s e l e c t :
4
o f
4
A L A R M 1
A L ARM 1 L A T CH
6-6
Configuration - Section 6