Satellite XT 4-20 mA Versions
Main Menu - Monitoring
The instrument is in the operating mode Mainte-
nance and the green LED is off.
Actuate the cursor keys <up> or <down> to move
forwards and backwards in the Main Menu.
Actuate the <set> key to enter the Monitoring Mode.
<Normal Condition>
This screen and the illuminated green LED indicate
that the instrument is in the Monitoring Mode and is
operating properly.
<Alarm 1 Condition>
This screen shows that Alarm Level 1 has been ex-
ceeded and that there is an actual gas concentration
of 0.07 ppm AsH3.
(f.i. Alarm 1 set at 0.05 ppm AsH3)
<Alarm 2 Condition>
This screen shows that Alarm Level 2 has been ex-
ceeded and that there is an actual gas concentration
of 0.12 ppm AsH3.
(f.i. Alarm 2 set at 0.10 ppm AsH3)
s e l e c t :
1
o f
4
MON I TOR I NG
M E N U
S a t e l l i t e X T
A s H 3
p p m
0 . 00
S a t e l l i t e X T
A s H 3
A L 1
p p m
0 . 07
S a t e l l i t e X T
A s H 3
A L 2
A L 1
p p m
0 . 12
3 - 2
3-2
Main Menu - Section 3