Dimension Series
MORLEY-IAS
User Manual
Document No.996-148-000-5, Revision: 5
Page 29
•
To disable or enable a type of output circuit, press
‘4’
and the display shows a menu of the types of
outputs. For example:
[U0 Disable/Enable] 1:Sounders
2:Fault Relays 3:Others
•
It is possible to enable or disable:
1. ALL Sounder Type Outputs.
2. ALL Fault Relay Type Outputs.
3. ALL Other Relay and Control Type Outputs
•
NOTE: The ‘Sounder’ device setting is used to differentiate between Sounder Type Outputs and
Other/Control Type Outputs. Refer to the Product Manual for more information.
•
Press
‘1’
,
‘2’
or
‘3’
are as required. The display then shows the following if the outputs are currently
enabled.
Disable ALL Sounder Outputs
Press
9
to Confirm X:Cancel
Disable ALL Fault Relay Outputs
Press
9
to Confirm X:Cancel
Disable ALL Relay and CTL Outputs
Press
9
to Confirm X:Cancel
•
The display shows the following if the outputs are currently disabled.
Enable ALL Sounder Outputs
Press
9
to Confirm X:Cancel
Enable ALL Fault Relay Outputs
Press
9
to Confirm X:Cancel
Enable ALL Relay and CTL Outputs
Press
9
to Confirm X:Cancel
•
Press
the
‘
9
’
key to confirm the enable / disable action and return to the enable / disable outputs
menu.
•
Press
‘X’
to return to the enable / disable outputs menu without making a change.