MORLEY-IAS
Dimension
Series
Page 16
Document No. 996-148-000-5, Revision: 5
User Manual
DISABLED 01/02 Z01 L1 A010 OPT 12:19
<Point-Location-Txt>
←
:back
R
:more
•
The display shows the disablement number and the total number of devices (points) in a disablement
condition in this zone (01/02), the Zone number (Z01), the loop number to which this device is
connected (L1), the address of this device on the loop (A010), the type of device (OPT), the time at
which the device was disabled (12:19) and the Point Location Text (20 character description) for this
device.
•
To view other points in disablement in this zone, press the
Ï
and
Ð
keys (Note: The ‘
R
: more’ option
is not shown if there is only one event, the ‘
↓
’ and ‘
↑
’ keys are shown for the first and last entries in the
list).
•
To return to the list of zones in a disablement condition, press the
Í
key.
4.3 Other Conditions – by event display option
•
The display always shows point details, for example:
FIRE 01/02 Z04 L1 A011 MCP 11:45
<Zone-Location-Text><Point-Location-Txt>
•
Each event is displayed for approximately 8 seconds, then the next event is displayed.
•
After every 2 events an appropriate instruction screen in displayed, for approximately 3 seconds, for
example:
USE ARROW KEYS TO VIEW MORE EVENTS
Ç
PREVIOUS EVENT
È
NEXT EVENT
4.3.1 Fire Alarm Conditions
•
If the control panel initiates an alarm condition, the FIRE LED Indicators will be illuminated and, if
appropriate, the relevant ZONE FIRE LED Indicators will illuminate. The internal buzzer will sound and
the alphanumeric display will scroll though each fire in turn, starting with the first fire. For example:
FIRE 01/02 Z04 L1 A011 MCP 11:45
<Zone-Location-Text><Point-Location-Txt>
•
The panel alphanumeric display may be configured by the installer to scroll though only those fires of
interest, and keep other fires in the background. Fire scrolling options are as follows:
•
1
st
fire only (default)
•
1
st
and last fire
•
First
4
fires
•
All
fires
•
Press
the
ÏÐ
keys to scroll through the fire list manually. If no key is pressed for 60 seconds, auto-
scrolling will resume.
•
Whilst fire alarm conditions are present (including panel fire alarms) then faults, disablements and
tests are not displayed.