Dimension Series
MORLEY-IAS
User Manual
Document No.996-148-000-5, Revision: 5
Page 25
5.3.1.4.1 Internal
Outputs
•
To select the option, press
‘1’
and the display shows to first available panel output circuit as follows:
[Internal Test] B:01 Sounder 1
9
:Start Test
R
:Select Output X:Exit
•
Press
the
Ï
and
Ð
keys to select the required output. A full list of available outputs is detailed in the
table below:
•
To start a test on the device and turn the output on, press the
‘
9
’
key. The display then shows:
[Internal Test] B:01 Sounder 1
Output test in progress X:Stop
•
Press
the
‘X’
key to stop the test.
Type of Output
Sounder Output 1
Sounder Output 2
Fault Relay
Fire Relay
Programmable Relay
Table 6 – Panel Internal Output Circuits
5.3.1.4.2 Loop
(SLC) Outputs
•
To select the option, press
‘2’
and the display shows to first available loop output circuit as follows:
[SLC Test] A008 SDR
9
:Start Test
R
:Select Output X:Exit
•
Press
the
Ï
and
Ð
keys to select the required output. The display shows the address of the device
(i.e. A008) and its type abbreviation code (i.e. SDR).
•
To start a test on the device and turn the output on, press the
‘
9
’
key. The display then shows:
[SLC Test] A008 SDR
Output test in progress X:Stop
•
Press
the
‘X’
key to stop the test.
•
Note that if the panel is equipped with 2 or 4 loops then the display will first prompt for selection of the
required signalling / detection loop.