70
To meet French regulations
, the reset mode should be set to “Manual-Duration-Reset” and the
duration must be at least 600 seconds. In this case, once the system is activated, the voice
alarm won’t be reset manually or automatically until the time has elapsed.
RK-ZONE8
1. Properties
Set the related working parameters as below:
Basic Setting
Basic setting includes the address and device name. The address should be the same as the
address set via the DIP switch on the rear panel of the device, which ranges from 1
–15. Please
refer to the
chapter “Address Setting” for related device settings. The device name can be
renamed by users. Ensure that the same name is not created twice within one project.
Speaker Lines
Speaker Lines is used to enable speaker lines. Click the checkbox as required:
means
enabled and
means disabled. Users can change the name and power of speaker lines. The
load power is only used as reference.
Selecting a speaker line and clicking the
button sets all the powers to be the same as the
current one
Trigger Mode of Contact Inputs
This table is used to set the trigger mode of each contact input as
Normally Open
or
Normally
Closed
.
If “
Normally Open
” is selected, when the switch of the third-party device is opened, the contact
input will be deactivated, and when the switch is closed, the contact input will be activated.
If “
Normally Closed
” is selected, when the switch of the third-party device is closed, the contact
input will be deactivated, and when the switch is opened, the contact input will be activated.