background image

APPEnDix ii. DETEcToR DRillinG TEMPlATE

4.345˝

6.190˝

 (157 mm)

 (110 mm)

Scale = 1:1

F300-29-00 

10 

I56-2425-007R

Summary of Contents for FireLite BEAM355

Page 1: ...g Standby 2mA Max 1 communication every 5 sec LED flashing SLC 24 V Max Alarm LED on 8 5mA Max Max Trouble LED on 4 5mA Max Max Alignment 20mA Max External Supply BEAM355S only VOLTAGE 15 to 32 VDC CURRENT 0 5A Max Remote Output alarm VOLTAGE 15 to 32 VDC NOTE Output voltage same as device input voltage CURRENT 15mA maximum 6mA minimum NOTE Output current is limited by 2 2Kohm resistor I56 2425 00...

Page 2: ... the detector and reflector cannot be mounted within 10 of each other The kit includes the hardware necessary to mount either a single transmitter receiver unit or a single reflector To mount the transmitter receiver the surface mount kit BEAMSMK must also be used If the transmitter receiver and the reflector require additional alignment range two kits are required The kit is not compatible with t...

Page 3: ...S 1 2 S MAX Tx Rx REFLECTOR C0256 00 Figure 4 Sloped ceiling peaked type 1 2 S S S 1 2 S 3 FT 0 9M MAX 3 FT 0 9M MAX MOUNT SPOT DETECTOR ANYWHERE IN THIS AREA Tx Rx REFLECTOR C0257 02 Mounting Locations Beam detectors require a stable mounting surface for proper operation A sur face that moves shifts vibrates or warps over time will cause false alarm or trouble conditions Initial selection of a pr...

Page 4: ...hrough panes of glass cannot be avoided some spe cific installation practices can help to minimize the effects of the glass These practices include avoid penetration of multiple panes of glass position the glass so that it is not perpendicular to the line of sight between the detector and the reflector A minimum of 10 off perpendicular should be considered and make certain that the glass is smooth...

Page 5: ...the product If the detector and reflector are mounted per Mounting Loca tions and Mounting Instructions sections of this manual and the alignment procedures are executed properly false alarms and nuisance trouble signals will be minimized Pre Alignment Checklist Ensure that both the detector and reflector are mounted securely to stable surfaces Ensure that all wiring is correct Ensure that termina...

Page 6: ...crease the electronic gain 4 Once satisfied that it is not possible to achieve a higher reading on the display depress the alignment switch to complete the fine adjustment step The digital display readout will turn OFF and the yellow LED will remain ON NOTE It may not be possible to achieve a value near 90 on the display during the last adjustment iteration The final value of the display will not ...

Page 7: ... illumination of the dual digital display To set the sensitivity depress the sensitivity button one time See Figure 10 Once the switch is pressed the digital display will illuminate and read the current sensitivity setting in percent obscuration To change the sensitivity continue to depress the sensitivity switch until the desired setting is achieved The digital display will turn off automatically...

Page 8: ... re ceiver unit or remotely using the remote test station The remote test station can be used with the BEAM355 BEAM355S beam smoke detector Follow instructions included with the test station for proper use See Figure 8 Remote Test Station for wiring diagram The BEAM355S is equipped with an integral sensitivity test feature that con sists of a calibrated test filter attached to a servo motor inside...

Page 9: ...tive objects in the pathway Trouble Beam Blockage Response Off 4 Quick Blinks Blink Blink Off Beam Blockage Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Blink Off Apply Power from discharged state Initialization alignment exit Off Blink until complete Blink Blink Off Depressing RESET switch after alignment Local Test BEAM355S Pass Result On Blinking the amount...

Page 10: ...Appendix II Detector Drilling Template 4 345 6 190 157 mm 110 mm Scale 1 1 F300 29 00 10 I56 2425 007R ...

Page 11: ...F300 29 00 11 I56 2425 007R ...

Page 12: ...5 512 140mm 8 465 215mm Appendix III Reflector Drilling Template Scale 1 1 F300 29 00 12 I56 2425 007R ...

Page 13: ...e reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in...