F300-29-00 

I56-2425-007R

remotely connected to the remote Alarm and Trouble outputs. These outputs 
mimic the functions of the detector’s red and yellow LEDs. In addition to these 
indicators, there is a dual digital display that reads 00 to 99. This display is 
used to indicate the signal strength of the beam in alignment mode and to 
indicate  the  sensitivity  setting  of  the  detector  in  percent  obscuration  when 
setting the sensitivity of the detector. No additional equipment is needed for 
alignment of the beam.

SPEciAl APPlicATionS

Due to the inherent capabilities of projected type beam detectors they are often 
installed in locations where spot-type detection is impractical. Projected type 
beam  smoke  detectors  are  ideally  suited  for  environmental  conditions  that 
might include high ceilings, dusty and dirty environments, or environments 
that experience temperature extremes. Often these conditions present special 
problems for the installation of spot-type detectors and even greater problems 
for their proper maintenance. Due to the inherent flexibility of mounting loca-
tions and large coverage area of projected type beam detectors often the condi-
tions above can be addressed or minimized.

Some examples of applications for beam detectors might include freezers, air-
craft hangars, cold storage warehouses, shipping warehouses, enclosed park-
ing facilities, sporting arenas and stadiums, concert halls, barns, or stables. 
Some  of  these  environments  might  be  considered  too  hostile  for  spot-type 

smoke detectors. If the environment is considered to be hostile then the colder 
alarm threshold settings should be used.

Before  installing  the  transmitter/receiver  unit  or  reflector  in  these  types  of 
applications special consideration should be given to ensure proper operation 
of the beam detector. The beam detector should not be installed in environ-
ments  where  there  is  no  temperature  control  and  condensation  or  icing  is 
likely. Condensation or icing of the reflector surface or the outer surface of 
the transmitter/receiver unit will obscure the light beam resulting in a false 
alarm. If elevated humidity levels and rapidly changing temperatures can be 
expected then condensation will likely form and the application should not be 
considered acceptable for the beam detector. The beam detector should not be 
installed in locations where the transmitter/receiver unit, the reflector, or the 
optical pathway between them may be exposed to outdoor conditions such as 
rain, snow, sleet, or fog. These conditions will impair the proper operation of 
the detector and must be avoided.

APPRovED AccESSoRiES

The following accessories can be purchased separately for use with this beam 
detector.

BEAMLRK

The  BEAMLRK  allows  Fire•Lite  reflected  beam  detectors  to  be  installed  at 

separations between 230 and 328 feet (70 to 100 meters). At these distances, 
four 8 inch×8 inch reflectors must be used to provide enough reflected infra-
red light. This kit includes 3 additional reflectors with new test scale legends. 
The reflector included with the transmitter/receiver unit is the fourth reflector 
to be used. This kit is not compatible with the multi-mount kit (BEAMMMK).

BEAMMMK

The BEAMMMK allows Fire•Lite reflected beam detectors and reflectors to be 

mounted to either a vertical wall or the ceiling. The kit allows for additional 
alignment range in cases where the detector and reflector cannot be mounted 
within 10° of each other. The kit includes the hardware necessary to mount 
either a single transmitter/receiver unit or a single reflector. (To mount the 
transmitter/receiver the surface mount kit, BEAMSMK, must also be used). If 
the transmitter/receiver and the reflector require additional alignment range 
two kits are required. The kit is not compatible with the long-range reflector 
kit (BEAMLRK). 

BEAMSMK

The BEAMSMK allows Fire•Lite reflected beam detectors to be mounted when 

surface wiring is used. This kit must be used when mounting the transmitter/
receiver unit with the multi-mount kit (BEAMMMK).

6500-MMK

The 6500-MMK provides a heavy-duty multi-mount bracket for installations 
prone to building movement or vibration.  It offers similar tilt and swivel flex-
ibility found on the BEAMMMK.  (To mount the transmitter/receiver to the 
6500-MMK, the surface mount kit, 6500-SMK, must be used).

6500-SMK

The  6500-SMK  allows  the  transmitter/receiver  to  be  mounted  to  the  6500-
MMK heavy duty multi-mount kit.

BEAMHK

The BEAMHK allows the transmitter/receiver unit to operate in environments 
prone to the formation of condensation. Condensation forming on the beam 
detector unit may result in trouble or false alarm conditions. BEAMHK will 
lessen the likelihood of condensation by maintaining the unit at a temperature 
that is slightly higher than the surrounding air. Please refer to the BEAMHK 
installation manual for operation instructions.

BEAMHKR

The BEAMHKR allows the reflector to operate in environments prone to the 
formation of condensation. Condensation forming on the reflector may result 
in trouble or false alarm conditions. BEAMHKR will lessen the likelihood of 
condensation  by  maintaining  the  reflector  at  a  temperature  that  is  slightly 
higher than surrounding air. The kit requires a 24V power supply. When used 
with the long-range reflector kit (BEAMLRK), it is necessary to purchase and 
install four BEAMHKR kits. Please refer to the BEAMHKR installation manual 
for operation instructions.

RTS451/KEY

The remote test accessory allows for the beam detector to be tested remotely. 
The test accessory provides test and reset functions and green and red LED’s 
that mimic the LED’s on the detector.

PARTS liST
Description 

Quantity

Transmitter/Receiver Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Paintable Trim Ring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Reflector 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Plug-in Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Isolator Shunts  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Instruction Manual  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Orange Sticky Paper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

PARTS DiAGRAM (noT To ScAlE)

TERMINAL BLOCK

ISOLATOR

SHUNT

PAINTABLE TRIM RING

C0306-00

DETEcToR PlAcEMEnT

This section of the manual discusses the placement of projected beam detec-
tors. Though this information is based upon industry expertise, it is intended 
to be used only as a technical guide. Always comply with the requirements of 
applicable codes and standards such as, NFPA 72, National Fire Alarm Code, 
as well as directives of the Authority Having Jurisdiction (AHJ).

Projected beam detectors are usually located with their beams parallel to the 
ceiling. However, they can be mounted vertically or at any angle to protect the 
area involved. Since beam detectors sense the smoke buildup over a distance, 
they are ideal for locations with high ceilings. They can also be mounted on a 
wall or ceiling below the level of a spot type detector, reducing the effects of 
air stratification. Some typical locations would include large areas with high 
ceilings such as atriums, warehouses, and factories. 

NOTE: 

Projected beam smoke detectors should always be mounted to sta-

ble mounting surfaces. See the MOUNTING LOCATION section for details.

Summary of Contents for FireLite BEAM355

Page 1: ...g Standby 2mA Max 1 communication every 5 sec LED flashing SLC 24 V Max Alarm LED on 8 5mA Max Max Trouble LED on 4 5mA Max Max Alignment 20mA Max External Supply BEAM355S only VOLTAGE 15 to 32 VDC CURRENT 0 5A Max Remote Output alarm VOLTAGE 15 to 32 VDC NOTE Output voltage same as device input voltage CURRENT 15mA maximum 6mA minimum NOTE Output current is limited by 2 2Kohm resistor I56 2425 00...

Page 2: ... the detector and reflector cannot be mounted within 10 of each other The kit includes the hardware necessary to mount either a single transmitter receiver unit or a single reflector To mount the transmitter receiver the surface mount kit BEAMSMK must also be used If the transmitter receiver and the reflector require additional alignment range two kits are required The kit is not compatible with t...

Page 3: ...S 1 2 S MAX Tx Rx REFLECTOR C0256 00 Figure 4 Sloped ceiling peaked type 1 2 S S S 1 2 S 3 FT 0 9M MAX 3 FT 0 9M MAX MOUNT SPOT DETECTOR ANYWHERE IN THIS AREA Tx Rx REFLECTOR C0257 02 Mounting Locations Beam detectors require a stable mounting surface for proper operation A sur face that moves shifts vibrates or warps over time will cause false alarm or trouble conditions Initial selection of a pr...

Page 4: ...hrough panes of glass cannot be avoided some spe cific installation practices can help to minimize the effects of the glass These practices include avoid penetration of multiple panes of glass position the glass so that it is not perpendicular to the line of sight between the detector and the reflector A minimum of 10 off perpendicular should be considered and make certain that the glass is smooth...

Page 5: ...the product If the detector and reflector are mounted per Mounting Loca tions and Mounting Instructions sections of this manual and the alignment procedures are executed properly false alarms and nuisance trouble signals will be minimized Pre Alignment Checklist Ensure that both the detector and reflector are mounted securely to stable surfaces Ensure that all wiring is correct Ensure that termina...

Page 6: ...crease the electronic gain 4 Once satisfied that it is not possible to achieve a higher reading on the display depress the alignment switch to complete the fine adjustment step The digital display readout will turn OFF and the yellow LED will remain ON NOTE It may not be possible to achieve a value near 90 on the display during the last adjustment iteration The final value of the display will not ...

Page 7: ... illumination of the dual digital display To set the sensitivity depress the sensitivity button one time See Figure 10 Once the switch is pressed the digital display will illuminate and read the current sensitivity setting in percent obscuration To change the sensitivity continue to depress the sensitivity switch until the desired setting is achieved The digital display will turn off automatically...

Page 8: ... re ceiver unit or remotely using the remote test station The remote test station can be used with the BEAM355 BEAM355S beam smoke detector Follow instructions included with the test station for proper use See Figure 8 Remote Test Station for wiring diagram The BEAM355S is equipped with an integral sensitivity test feature that con sists of a calibrated test filter attached to a servo motor inside...

Page 9: ...tive objects in the pathway Trouble Beam Blockage Response Off 4 Quick Blinks Blink Blink Off Beam Blockage Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Blink Off Apply Power from discharged state Initialization alignment exit Off Blink until complete Blink Blink Off Depressing RESET switch after alignment Local Test BEAM355S Pass Result On Blinking the amount...

Page 10: ...Appendix II Detector Drilling Template 4 345 6 190 157 mm 110 mm Scale 1 1 F300 29 00 10 I56 2425 007R ...

Page 11: ...F300 29 00 11 I56 2425 007R ...

Page 12: ...5 512 140mm 8 465 215mm Appendix III Reflector Drilling Template Scale 1 1 F300 29 00 12 I56 2425 007R ...

Page 13: ...e reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in...

Reviews: