background image

line of sight to the transmitter/receiver unit. The maximum tolerance for non-
perpendicular mounting locations is 10°. See Figure 5b. If the reflector cannot 
be mounted within 10° of the transmitter/receiver unit then the multi-mount 
kit (BEAMMMK) or the heavy-duty multi-mount kit (6500-MMK) may be used 
to provide greater angular adjustment of the transmitter/receiver unit. If the 
perpendicular plane of the reflector cannot be mounted within 10° of the op-
tical line of sight then the multi-mount kit can be used for the reflector. See 
BEAMMMK or 6500-MMK instructions. 

To  aid  in  locating  the  reflector  in  the  alignment  mirror  at  long  distances  a 
bright orange sticky backed piece of paper is provided. Remove the protective 
backing from the orange sticker. Temporarily affix the orange paper next to 
the reflector using the sticky backing of the paper. The location of the sticky 
paper is not critical. It may be placed anywhere near the reflector as long as it 
not covering the reflective surface of the reflector. This sticky paper should be 
removed once the installation is completed.

fiGuRE 5A. REflEcToR MounTinG GuiDElinES

WA

LL

REFLECT

OR

ACCEPTABLE MOUNTING

LOCATIONS FOR REFLECTOR

10

10

C0258-00

fiGuRE 5B. REflEcToR MounTinG GuiDElinES

10  MAXIMUM

OPTICAL LINE OF SIGHT

REFLECTOR

C0259-00

MounTinG conSiDERATionS foR SinGlE EnDED BEAM DETEcToRS

There must be a permanent clear line of vision between the detector and the 
reflector. Reflective objects must not be near the line of vision between the 
detector and reflector. Reflective objects too near to the line of sight can reflect 
the light beam from the transmitter to the receiver. If this occurs, the detector 
will not be able to distinguish these reflections from those of the reflector and 
the protected space will be compromised. Reflective objects should be a mini-
mum of 15 inches (38.1cm) from the line of sight between the detector and 
reflector. In cases where reflective objects cannot be avoided, the complete re-
flector blockage test can be used to determine if the installation is acceptable. 
See Testing and Maintenance Section of this manual.

Light sources of extreme intensity such as sunlight and halogen lamps, if di-
rected at the receiver, can cause a dramatic signal change resulting in fault 
and alarm signals. To prevent this problem direct sunlight into the transmitter/
receiver unit should be avoided. There should be a minimum of 10° between 
the  pathway  of  the  light  source  and  detector  and  the  line  of  sight  between 
detector and reflector.

Operation  of  the  detector  through  panes  of  glass  should  be  avoided.  Since 
single ended beam detectors operate on a reflection principle, a pane of glass 
perpendicular to the line of sight between the detector and the reflector can 
reflect the light beam from the transmitter to the receiver. If this occurs, the 
detector will not be able to distinguish these reflections from those of the re-
flector and the protected space will be compromised. 

Panes of glass will also absorb some of the light as it passes through it. This 
absorption of light will reduce the acceptable installed distance between the 

detector and the reflector.

In cases where operation through panes of glass cannot be avoided some spe-
cific installation practices can help to minimize the effects of the glass. These 
practices include: avoid penetration of multiple panes of glass, position the 
glass so that it is not perpendicular to the line of sight between the detector 
and the reflector, (A minimum of 10° off perpendicular should be considered), 
and make certain that the glass is smooth, clear and mounted securely. The 
complete reflector blockage test can be used to determine if the installation is 
acceptable. See Testing and Maintenance Section of this manual.

Where high ceilings (in excess of 30 feet or 9.1 meters) are present additional 
beam smoke detectors mounted at multiple heights may be required to detect 
smoke at lower levels.  See the Detector Placement section in this installation 
manual.

wiRinG inSTAllATion GuiDElinES

Always install all wiring in compliance with the National Electrical Code, and/
or the applicable local codes, and any special requirements of the local au-
thority having jurisdiction. Proper wire gauges and suitable means for strain 
relief should be used. The conductors used to connect beam smoke detectors 
to control panels and accessory devices should be color-coded to reduce the 
likelihood of wiring errors. Improper connections can prevent a system from 
responding properly in the event of a fire.

Installation wire used for the beam detector shall be no smaller than 22 AWG 
(1.0 mm2). For best system performance, all wiring should be twisted pair and 
installed in separate grounded conduit. Do NOT mix fire system wiring in the 
same conduit as any other electrical wiring. Shielded cable may be used to 
provide additional protection against electrical interference.

When installing the beam smoke detector in applications where the head unit 
will  be  mounted  to  either  a  wall  or  the  ceiling  using  the  multi-mount  kits 
(BEAMMMK or 6500-MMK) flexible conduit will be used. The surface mount 
kits  (BEAMSMK  or  6500-SMK)  and  multi-mount  kits  (BEAMMMK  or  6500-
MMK) must be installed with the cable before wiring the unit, according to 
the instructions supplied with the kit.

When the detector has been mounted over a recessed junction box, all wiring 
should be routed out of the box and behind the detector to the bottom of the 
detector  where  the  terminal  blocks  are  located.  When  installing  the  wiring 
in the junction box be sure to leave enough wire in the box to connect to the 
terminal blocks. (Approximately 9 inch (23cm) of wire outside of the junction 
box will be required for proper installation). All wiring to the detector is done 
via  pluggable  terminal  blocks.  In  order  to  properly  make  electrical  connec-
tions strip approximately 1/4 inch (6mm) of insulation from the end of the 
wire, sliding the bare end of the wire under the clamping plate screw. 

Figure  6  shows  all  the  wiring  connections  to  the  transmitter/receiver  unit. 
Figure 7 shows the proper wiring diagram for either class A or class B opera-
tion. Figure 8 shows the connections that are necessary when using one of 
the optional remote test stations. Figure 9 shows the remote output for alarm 
indication.

WARNING:

  Disable the zone or system before applying power to the beam 

detector  to  prevent  unwanted  alarms.  When  applying  power  to 
the beam detector before the alignment procedure has been com-
pleted the detector may enter alarm or fault.

F300-29-00 

I56-2425-007R

Summary of Contents for FireLite BEAM355

Page 1: ...g Standby 2mA Max 1 communication every 5 sec LED flashing SLC 24 V Max Alarm LED on 8 5mA Max Max Trouble LED on 4 5mA Max Max Alignment 20mA Max External Supply BEAM355S only VOLTAGE 15 to 32 VDC CURRENT 0 5A Max Remote Output alarm VOLTAGE 15 to 32 VDC NOTE Output voltage same as device input voltage CURRENT 15mA maximum 6mA minimum NOTE Output current is limited by 2 2Kohm resistor I56 2425 00...

Page 2: ... the detector and reflector cannot be mounted within 10 of each other The kit includes the hardware necessary to mount either a single transmitter receiver unit or a single reflector To mount the transmitter receiver the surface mount kit BEAMSMK must also be used If the transmitter receiver and the reflector require additional alignment range two kits are required The kit is not compatible with t...

Page 3: ...S 1 2 S MAX Tx Rx REFLECTOR C0256 00 Figure 4 Sloped ceiling peaked type 1 2 S S S 1 2 S 3 FT 0 9M MAX 3 FT 0 9M MAX MOUNT SPOT DETECTOR ANYWHERE IN THIS AREA Tx Rx REFLECTOR C0257 02 Mounting Locations Beam detectors require a stable mounting surface for proper operation A sur face that moves shifts vibrates or warps over time will cause false alarm or trouble conditions Initial selection of a pr...

Page 4: ...hrough panes of glass cannot be avoided some spe cific installation practices can help to minimize the effects of the glass These practices include avoid penetration of multiple panes of glass position the glass so that it is not perpendicular to the line of sight between the detector and the reflector A minimum of 10 off perpendicular should be considered and make certain that the glass is smooth...

Page 5: ...the product If the detector and reflector are mounted per Mounting Loca tions and Mounting Instructions sections of this manual and the alignment procedures are executed properly false alarms and nuisance trouble signals will be minimized Pre Alignment Checklist Ensure that both the detector and reflector are mounted securely to stable surfaces Ensure that all wiring is correct Ensure that termina...

Page 6: ...crease the electronic gain 4 Once satisfied that it is not possible to achieve a higher reading on the display depress the alignment switch to complete the fine adjustment step The digital display readout will turn OFF and the yellow LED will remain ON NOTE It may not be possible to achieve a value near 90 on the display during the last adjustment iteration The final value of the display will not ...

Page 7: ... illumination of the dual digital display To set the sensitivity depress the sensitivity button one time See Figure 10 Once the switch is pressed the digital display will illuminate and read the current sensitivity setting in percent obscuration To change the sensitivity continue to depress the sensitivity switch until the desired setting is achieved The digital display will turn off automatically...

Page 8: ... re ceiver unit or remotely using the remote test station The remote test station can be used with the BEAM355 BEAM355S beam smoke detector Follow instructions included with the test station for proper use See Figure 8 Remote Test Station for wiring diagram The BEAM355S is equipped with an integral sensitivity test feature that con sists of a calibrated test filter attached to a servo motor inside...

Page 9: ...tive objects in the pathway Trouble Beam Blockage Response Off 4 Quick Blinks Blink Blink Off Beam Blockage Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Blink Off Apply Power from discharged state Initialization alignment exit Off Blink until complete Blink Blink Off Depressing RESET switch after alignment Local Test BEAM355S Pass Result On Blinking the amount...

Page 10: ...Appendix II Detector Drilling Template 4 345 6 190 157 mm 110 mm Scale 1 1 F300 29 00 10 I56 2425 007R ...

Page 11: ...F300 29 00 11 I56 2425 007R ...

Page 12: ...5 512 140mm 8 465 215mm Appendix III Reflector Drilling Template Scale 1 1 F300 29 00 12 I56 2425 007R ...

Page 13: ...e reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in...

Reviews: