F300-29-00
9
I56-2425-007R
APPEnDix i. oPERATion MoDES AnD TRouBlEShooTinG GuiDE
Modes
*Red
See
Note
Below
Yellow and
Remote Trouble
Output
*Green
See
Note
Below
Remote
Alarm
Output
Dual Digital Display
Initiating means
Comments & Troubleshooting Tips
Normal
Off
Off
Blink
Blink
Off
Successful
completion of
initialization or
detector reset
Alignment
Off
On
Blink
Blink
On, Relative amount
of signal 0-99, or – if
automatic gain resetting,
or Lo if signal is too low
Alignment Switch
Alarm
On
Off
Off
On
Off
Smoke, Test Filter,
RTS451 Test
Stations
Trouble-Drift
Comp Elevated
Signal
Off
3 Quick Blinks
Blink
Blink
Off
Long Term Drift
Reference Out of
Range
•
Sunlight into detector or reflector.
•
Re-Align detector.
Trouble-
Drift Comp
Reduced
Signal
Off
2 Quick Blinks
Blink
Blink
Off
Long Term Drift
Reference Out of
Range
•
Clean detector and reflector.
Trouble-Signal
Over Range
Off
2 Quick Blinks
Blink
Blink
Off
Increase of
Reflected Signal
•
Inspect line of sight between
detector and reflector for reflective
objects in the pathway.
Trouble-Beam
Blockage
Response
Off
4 Quick Blinks
Blink
Blink
Off
Beam Blockage
•
Remove blockage.
•
Faulty unit.
Initialization-
Power on
Off
Blink until complete Blink
Blink
Off
Apply Power from
discharged state.
Initialization-
alignment exit
Off
Blink until complete Blink
Blink
Off
Depressing
RESET switch
after alignment
Local Test
(BEAM355S)
Pass Result
On
Blinking the amount
of drift used
Off
On
Off
Panel or RTS451/
KEY
Remains in alarm until reset or time-out
Local Test
(BEAM355S)
Fail Result
Off
On until reset or
time-out
Blink
Blink
Off
Panel or RTS451/
KEY test input
Remains in fault until reset or time-out
Local Test
(BEAM355)
Fail
Off
On until reset or
time-out
Blink
Blink
Off
Panel or RTS451/
KEY test input
Remains in fault until reset or time-out
Local Test
(BEAM355)
Pass Result
On
Blinking the amount
of drift used
Off
On
Off
Panel or RTS451/
KEY
Remains in alarm until reset or time-out
Note: Green and Red LEDs are controlled by the control panel.
Blinks output by Yellow LED and Remote Trouble Output once the device has
passed a local remote test:
Percent the detector has drifted
Number of blinks output
<10%
None
<20%
1
<30%
2
<40%
3
<50%
4
<60%
5
<70%
6
<80%
7
<90%
8
<100%
9
Summary of Contents for FireLite BEAM355