background image

2.0

1.5

1.0

0.5

0.0

0

25% SETTING

30% SETTING

40% SETTING

50% SETTING

50

100

150

200

250

300

350

OBSCURA

TION (%/FT

.)

SENSITIVITY IN PERCENT PER FOOT VS. DISTANCE

(ASSUMES UNIFORM SMOKE DISTRIBUTION)

DISTANCE IN FEET

C0268-00

SEnSiTiviTy TESTinG

NOTE: 

Before testing, notify the proper authorities that the smoke detector 

system is undergoing maintenance, and therefore the system will be tempo-
rarily out of service. Disable the zone or system undergoing maintenance to 
prevent unwanted alarms.
Detectors must be tested after installation and following periodic maintenance. 
The sensitivity of the BEAM355/BEAM355S may be tested as follows:

NOTE: 

Before testing the detector, check for the presence of the flashing 

green LED at the receiver, making sure not to disturb or block the beam. If it 
does not flash and the detector is not in trouble or alarm, power has been lost 
to the detector (check the wiring).

A. Calibrated Test Filter

The sensitivity of the detector can be tested using an opaque material to cover 
the reflector by an amount indicated by the graduated scale on the reflector. 
(Due to the high optical efficiency of the reflector the selection of the opaque 
material  used  to  block  the  reflector  is  not  critical.  Acceptable  materials  in-
clude, but aren’t limited to, this manual or the cardboard packaging inserts.)

Refer to Figure 14 for this procedure.

1.   Verify  the  sensitivity  setting  of  the  detector  in  %  obscuration.  See  the 

Sensitivity Selection section of this manual for sensitivity determination 
if sensitivity is unknown.

2.   Place the blocking material over the reflector, lining it up with the gradu-

ated marks that are 10 less than the detector’s setting in % obscuration. 
The detector should not alarm or fault. Keep the material in place for a 
minimum of 1 minute.

3.   Place the blocking material over the reflector lining it up with the gradu-

ated marks that are 10 more than the detectors setting in % obscuration. 
The detector should enter alarm within 1 minute.

fiGuRE 14. REflEcToR TEST cARD PRocEDuRE

LINE UP EDGE OF

TEST CARD WITH

APPROPRIATE

OBSCURATION LEVEL

MOVE TEST CARD TO DESIRED AMOUNT OF OBSCURATION

C0267-00

4.   The detector can be reset with the reset switch on the detector unit or 

remote reset.

5.   Notify the proper authorities that the system is back on line.
If the detector fails this test several steps should be taken to determine if the 
detector is faulty or simply needs to be re-adjusted before returning the unit. 
These steps include:

1.   Verify  all  wiring  connections  and  appropriate  power  is  applied  to  the 

detector.

2.   Verify that the optical line of sight is free from obstructions and reflective 

objects.

3.   Apply the maintenance procedure in this manual. Repeat the test proce-

dure. If the detector still fails the test procedure proceed with step 4.

4.   Repeat the alignment procedure in this manual. If the alignment proce-

dure is successful repeat the test procedure. If the detector still fails the 
test it should be returned.

NOTE: 

For the BEAM355S the external power supply must be connected 

for the test switch to work.

B. Test Switch 

The detector can be tested using the local test switch on the transmitter/re-
ceiver unit or remotely using the remote test station.

The  remote  test  station  can  be  used  with  the  BEAM355/BEAM355S  beam 
smoke detector. Follow instructions included with the test station for proper 
use. See Figure 8 (Remote Test Station) for wiring diagram.

The BEAM355S is equipped with an integral sensitivity test feature that con-
sists of a calibrated test filter attached to a servo motor inside the detector 
optics. When a test is initiated using the remote test station or local test switch 
the test filter is moved in the pathway of the light beam. The on-board micro-
processor then determines if the proper level of signal reduction is received 
at the receiver. If the proper level of signal reduction is received the detector 
will enter alarm. If the proper level of signal reduction was not achieved, indi-
cating that the sensitivity of the detector is out of tolerance, the detector will 
enter the trouble condition.

Always perform a complete reflector blockage test as in step 4 of the Instal-
lation/Alignment procedure to ensure that the pathway between the detector 
and reflector is clear.

NOTE: 

For  the  BEAM355  this  test  does  not  satisfy  the  requirements  of 

NFPA72  for  periodic  maintenance  and  sensitivity  verification  of  beam  type 
detectors. For the BEAM355S this test in conjunction with the complete reflec-
tor blockage test (see step 4 of the Installation/Alignment procedure in this 
manual) does satisfy the requirements of NFPA72 for periodic maintenance 
and sensitivity verification of beam type detectors.
If the detector fails this test several steps should be taken to determine if the 
detector is faulty or simply needs to be re-adjusted before returning the unit. 
These steps include:

1.   Verify  all  wiring  connections  and  appropriate  power  is  applied  to  the 

detector.

2.   Verify that the optical line of sight is free from obstructions and reflective 

objects.

3.   Apply the maintenance procedure in this manual. Repeat the test proce-

dure. If the detector still fails the test procedure proceed with step 4.

4.   Repeat the alignment procedure in this manual. If the alignment proce-

dure is successful repeat the test procedure. If the detector still fails the 
test it should be returned for repair.

NOTE: 

For the BEAM355S, the external power supply must be connected 

for the test switch to work.

MAinTEnAncE

NOTE: 

Before cleaning the detector, notify the proper authorities that the 

smoke detector system is undergoing maintenance, and therefore the system 
will  be  temporarily  out  of  service.  Disable  the  zone  or  system  undergoing 
maintenance to prevent unwanted alarms.
1.    Carefully  clean  the  outer  housing  lens  face.  A  damp  soft  cloth  with  a 

mild soap may be used. Avoid products with solvents or ammonia.

2.    Carefully clean the reflector. A damp soft cloth with a mild soap may be 

used. Avoid products with solvents or ammonia.

3.    Notify the proper authorities that the system is back on line.

PAinTinG

The outer aesthetic ring may be painted using a spray or brush type paint of 
appropriate type. See specification section of this manual for paint types.

NOTE: 

Never paint the flat lens surface of the outer housing.

SPEciAl noTE REGARDinG SMokE DETEcToR GuARDS

Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.

F300-29-00 

I56-2425-007R

Summary of Contents for FireLite BEAM355

Page 1: ...g Standby 2mA Max 1 communication every 5 sec LED flashing SLC 24 V Max Alarm LED on 8 5mA Max Max Trouble LED on 4 5mA Max Max Alignment 20mA Max External Supply BEAM355S only VOLTAGE 15 to 32 VDC CURRENT 0 5A Max Remote Output alarm VOLTAGE 15 to 32 VDC NOTE Output voltage same as device input voltage CURRENT 15mA maximum 6mA minimum NOTE Output current is limited by 2 2Kohm resistor I56 2425 00...

Page 2: ... the detector and reflector cannot be mounted within 10 of each other The kit includes the hardware necessary to mount either a single transmitter receiver unit or a single reflector To mount the transmitter receiver the surface mount kit BEAMSMK must also be used If the transmitter receiver and the reflector require additional alignment range two kits are required The kit is not compatible with t...

Page 3: ...S 1 2 S MAX Tx Rx REFLECTOR C0256 00 Figure 4 Sloped ceiling peaked type 1 2 S S S 1 2 S 3 FT 0 9M MAX 3 FT 0 9M MAX MOUNT SPOT DETECTOR ANYWHERE IN THIS AREA Tx Rx REFLECTOR C0257 02 Mounting Locations Beam detectors require a stable mounting surface for proper operation A sur face that moves shifts vibrates or warps over time will cause false alarm or trouble conditions Initial selection of a pr...

Page 4: ...hrough panes of glass cannot be avoided some spe cific installation practices can help to minimize the effects of the glass These practices include avoid penetration of multiple panes of glass position the glass so that it is not perpendicular to the line of sight between the detector and the reflector A minimum of 10 off perpendicular should be considered and make certain that the glass is smooth...

Page 5: ...the product If the detector and reflector are mounted per Mounting Loca tions and Mounting Instructions sections of this manual and the alignment procedures are executed properly false alarms and nuisance trouble signals will be minimized Pre Alignment Checklist Ensure that both the detector and reflector are mounted securely to stable surfaces Ensure that all wiring is correct Ensure that termina...

Page 6: ...crease the electronic gain 4 Once satisfied that it is not possible to achieve a higher reading on the display depress the alignment switch to complete the fine adjustment step The digital display readout will turn OFF and the yellow LED will remain ON NOTE It may not be possible to achieve a value near 90 on the display during the last adjustment iteration The final value of the display will not ...

Page 7: ... illumination of the dual digital display To set the sensitivity depress the sensitivity button one time See Figure 10 Once the switch is pressed the digital display will illuminate and read the current sensitivity setting in percent obscuration To change the sensitivity continue to depress the sensitivity switch until the desired setting is achieved The digital display will turn off automatically...

Page 8: ... re ceiver unit or remotely using the remote test station The remote test station can be used with the BEAM355 BEAM355S beam smoke detector Follow instructions included with the test station for proper use See Figure 8 Remote Test Station for wiring diagram The BEAM355S is equipped with an integral sensitivity test feature that con sists of a calibrated test filter attached to a servo motor inside...

Page 9: ...tive objects in the pathway Trouble Beam Blockage Response Off 4 Quick Blinks Blink Blink Off Beam Blockage Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Blink Off Apply Power from discharged state Initialization alignment exit Off Blink until complete Blink Blink Off Depressing RESET switch after alignment Local Test BEAM355S Pass Result On Blinking the amount...

Page 10: ...Appendix II Detector Drilling Template 4 345 6 190 157 mm 110 mm Scale 1 1 F300 29 00 10 I56 2425 007R ...

Page 11: ...F300 29 00 11 I56 2425 007R ...

Page 12: ...5 512 140mm 8 465 215mm Appendix III Reflector Drilling Template Scale 1 1 F300 29 00 12 I56 2425 007R ...

Page 13: ...e reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in...

Reviews: