Some fire codes specify spacing on a given center-to-center distance between 
detectors under ideal conditions. This spacing is based on rooms with smooth 
ceilings  and  no  physical  obstructions  between  the  contents  being  protected 
and  the  detectors.  Moreover,  they  are  also  based  on  a  maximum  ceiling 
height, and on the assumption that the value and the combustible nature of 
the contents of the room being protected do not warrant greater protection or 
closer spacing.

In a room with a smooth ceiling, detectors should be spaced horizontally be-
tween 30 and 60 feet (9.1 to 18.3m). One-half that spacing between the beam 
and the sidewall may be used as a guide. See Figure 1. The beam detector 
can be mounted with the transmitter/receiver on one wall and the reflector 
on the opposite wall, or both suspended from the  ceiling, or any wall/ceiling 
combination. In the case of the ceiling mount, the distance from the end walls 
should not exceed one-quarter of the selected spacing (7.5 ft. [2.3m] maxi-
mum if the spacing is 30 ft. [9.1m]). See Figure 2.

fiGuRE 1. SPAcinG foR SMooTh cEilinG (SiDE viEw):

1

/

2

 S

S

12 IN. MIN.

(0.3M)

30’ (9.1M) MAX

TO FIRST

DETECTORS

WALL

10’ (3.0M)

MIN.

TYPICAL

C0254-02

fiGuRE 2. SPAcinG foR SMooTh cEilinG (ToP viEw):

16 FT. (5M) MINIMUM

328 FT. (100M) MAXIMUM

Tx/Rx

REFLECTOR

S

Tx/Rx

REFLECTOR

1

/

2

 S MAXIMUM

1

/

4

 S

MAX.

C0255-00

In the case of peaked or sloped ceilings, codes may specify spacing of detec-
tors by using horizontal spacing from the peak of the roof or ceiling. Figures 
3  and  4  show  the  spacing  for  both  the  shed  type  and  peaked  type  sloped 
ceilings.

On  smooth  ceilings,  beam  smoke  detectors  should  generally  be  mounted  a 
minimum of 12 inches (0.3m) from the ceiling or beneath structural obstruc-
tions  such  as  joists,  ducts,  etc.  See  Figure  1.  In  many  cases,  however,  the 
location and sensitivity of the detectors shall be the result of an engineering 
evaluation that includes the following: ceiling heights above 30 feet (9.1 m) - 
refer to the “Single-Ended Reflected Beam Smoke Detector” application guide 
A05-0095  for  more  information  regarding  the  effects  of  stratification,  struc-
tural features, size and shape of the room and bays, occupancy and uses of the 
area, ceiling height, ceiling shape, surface and obstructions, ventilation, ambi-
ent environment, burning characteristics of the combustible materials present, 
and the configuration of the contents in the area to be protected.

fiGuRE 3. SloPED cEilinG (ShED TyPE):

S

3 FT.

(0.9M)MAX.

S

1

/

2

 S MAX.

Tx/Rx

REFLECTOR

C0256-00

fiGuRE 4. SloPED cEilinG (PEAkED TyPE):

1

/

2

 S

S

S

1

/

2

 S

3 FT. (0.9M

)

MAX.

3 FT. (0.9M

)

MAX.

MOUNT SPOT 

DETECTOR 

ANYWHERE IN

THIS AREA

Tx/Rx

REFLECTOR

C0257-02

MounTinG locATionS

Beam detectors require a stable mounting surface for proper operation. A sur-
face that moves, shifts, vibrates, or warps over time will cause false alarm or 
trouble conditions. Initial selection of a proper mounting surface will elimi-
nate false alarms and nuisance trouble signals.

Mount  the  detector  on  a  stable  mounting  surface,  such  as  brick,  concrete, 
a  sturdy  load-bearing  wall,  support  column,  structural  beam,  or  other  sur-
face that is not expected to experience vibration or movement over time. DO 
NOT MOUNT the beam detector on corrugated metal walls, sheet metal walls, 
external  building  sheathing,  external  siding,  suspended  ceilings,  steel  web 
trusses, rafters, nonstructural beam, joists, or other such surfaces.

In  cases  where  only  one  stable  mounting  surface  as  defined  above  can  be 
used, the transmitter/receiver unit should be mounted to the stable surface 
and  the  reflector  should  be  mounted  to  the  less  stable  surface.  The  reflec-
tor has a much greater tolerance for the unstable mounting locations defined 
above.

MounTinG inSTRucTionS

The transmitter/receiver unit may be mounted over a recessed junction box. 
The cavity behind the detector is then used for routing of the wiring from the 
junction box to the terminal blocks on the detector. The transmitter/receiver 
unit should be mounted to the wall such that unit covers the recessed junc-
tion box in the wall completely. If the junction box is not recessed then you 
may use the surface mount kit (BEAMSMK). See the BEAMSMK installation 
instructions for surface mounting instructions. The transmitter/receiver unit 
can be mounted to the wall using the supplied drilling template (see Appendix 
II). The detector base has 4 primary mounting keyholes, one in each corner of 
the base. All four hole locations should be used to provide a secure mounting. 
The outer housing of the beam detector is held to the base using four screws. 
In order to mount the detector you must remove the outer housing first.

The reflector can be mounted to the wall using the supplied drilling template 
(see Appendix III). The reflector has 4 mounting holes, one in each corner. 
All  four  hole  locations  should  be  used  to  provide  a  secure  mounting.  The 
reflector  must  be  mounted  such  that  it  is  within  10°  in  both  the  X  and  Y 
planes of the transmitter/receiver unit. See Figure 5a. The reflector must also 
be  mounted  such  that  plane  of  the  reflector  is  perpendicular  to  the  optical 

F300-29-00 

I56-2425-007R

Summary of Contents for FireLite BEAM355

Page 1: ...g Standby 2mA Max 1 communication every 5 sec LED flashing SLC 24 V Max Alarm LED on 8 5mA Max Max Trouble LED on 4 5mA Max Max Alignment 20mA Max External Supply BEAM355S only VOLTAGE 15 to 32 VDC CURRENT 0 5A Max Remote Output alarm VOLTAGE 15 to 32 VDC NOTE Output voltage same as device input voltage CURRENT 15mA maximum 6mA minimum NOTE Output current is limited by 2 2Kohm resistor I56 2425 00...

Page 2: ... the detector and reflector cannot be mounted within 10 of each other The kit includes the hardware necessary to mount either a single transmitter receiver unit or a single reflector To mount the transmitter receiver the surface mount kit BEAMSMK must also be used If the transmitter receiver and the reflector require additional alignment range two kits are required The kit is not compatible with t...

Page 3: ...S 1 2 S MAX Tx Rx REFLECTOR C0256 00 Figure 4 Sloped ceiling peaked type 1 2 S S S 1 2 S 3 FT 0 9M MAX 3 FT 0 9M MAX MOUNT SPOT DETECTOR ANYWHERE IN THIS AREA Tx Rx REFLECTOR C0257 02 Mounting Locations Beam detectors require a stable mounting surface for proper operation A sur face that moves shifts vibrates or warps over time will cause false alarm or trouble conditions Initial selection of a pr...

Page 4: ...hrough panes of glass cannot be avoided some spe cific installation practices can help to minimize the effects of the glass These practices include avoid penetration of multiple panes of glass position the glass so that it is not perpendicular to the line of sight between the detector and the reflector A minimum of 10 off perpendicular should be considered and make certain that the glass is smooth...

Page 5: ...the product If the detector and reflector are mounted per Mounting Loca tions and Mounting Instructions sections of this manual and the alignment procedures are executed properly false alarms and nuisance trouble signals will be minimized Pre Alignment Checklist Ensure that both the detector and reflector are mounted securely to stable surfaces Ensure that all wiring is correct Ensure that termina...

Page 6: ...crease the electronic gain 4 Once satisfied that it is not possible to achieve a higher reading on the display depress the alignment switch to complete the fine adjustment step The digital display readout will turn OFF and the yellow LED will remain ON NOTE It may not be possible to achieve a value near 90 on the display during the last adjustment iteration The final value of the display will not ...

Page 7: ... illumination of the dual digital display To set the sensitivity depress the sensitivity button one time See Figure 10 Once the switch is pressed the digital display will illuminate and read the current sensitivity setting in percent obscuration To change the sensitivity continue to depress the sensitivity switch until the desired setting is achieved The digital display will turn off automatically...

Page 8: ... re ceiver unit or remotely using the remote test station The remote test station can be used with the BEAM355 BEAM355S beam smoke detector Follow instructions included with the test station for proper use See Figure 8 Remote Test Station for wiring diagram The BEAM355S is equipped with an integral sensitivity test feature that con sists of a calibrated test filter attached to a servo motor inside...

Page 9: ...tive objects in the pathway Trouble Beam Blockage Response Off 4 Quick Blinks Blink Blink Off Beam Blockage Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Blink Off Apply Power from discharged state Initialization alignment exit Off Blink until complete Blink Blink Off Depressing RESET switch after alignment Local Test BEAM355S Pass Result On Blinking the amount...

Page 10: ...Appendix II Detector Drilling Template 4 345 6 190 157 mm 110 mm Scale 1 1 F300 29 00 10 I56 2425 007R ...

Page 11: ...F300 29 00 11 I56 2425 007R ...

Page 12: ...5 512 140mm 8 465 215mm Appendix III Reflector Drilling Template Scale 1 1 F300 29 00 12 I56 2425 007R ...

Page 13: ...e reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in...