Diagnostic Check
Ensure that the Device Index switches on the IOTA were not intentionally set to zero to initiate a
Device Index/IP Address reset.
Cause 1
Device Index switches set to zero.
Solution
Change Device Index switches to correct setting.
Cause 2
The module is defective.
Solution
Replace the module.
If Device Index switch setting matches Device Index number in 4-character display upon PGM power
up, the removed module is defective. Otherwise, go to Cause 3.
Cause 3
The IOTA is defective.
Solution
Replace the IOTA.
If Device Index switch setting matches Device Index number in 4-character display upon PGM power
up, the removed IOTA is defective.
13 PROFIBUS GATEWAY MODULE (PGM) TROUBLESHOOTING
261
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...