Options in
PA Status
Usage
column
Applicable
for
Description
Update Ch
status
Input
channels
When you select this option, the status is read from raw data and channel status is
updated. The channel’s
Status
column and the
PA Status
column display the actual
device status.
The
Update channel status
option is selected by default.
Update Ch
status and
alarm
Input
channels
When you select this option, the status is read from raw data. The
Status
column and the
PA Status
column display the actual device status. In addition, an alarm
Data status
below limit in PDC
is reported if the status is below the defined first acceptable PA
status value.
Attention
You must define the first acceptable PA status value while configuring the DSB
(GENPADSB/GENPAGWDSB) for the alarms to be reported when the channel
status is below the first acceptable PA status value.
Set output
status
Output
channels
When you select this option, the channel status is always set to
GoodCasc_NonSpecific
.
However, the
PA Status
column displays the value
Not Applicable
. If the PA device is
removed from the network, the
PA Status
column displays the value
Not Available
.
The
Set output status
option is selected by default.
Attention
For GENPAGWDSB, the configurable output channel status is always set to
GoodCas_NonSpecific
even in the absence of the device. However, the extended
diagnosis reports the device unavailability. With the extended diagnosis and the
user-defined alarms, you can set the PDC channel state to
Bad_NonSpecific
for
that specific channel.
7.16.4 CEAG DSB specific PDC configuration guidelines
The following list summarizes the CEAG DSB specific PDC configuration guidelines that you must remember
while configuring the CEAG DSB PDC.
• The number of PDCs supported by CEAGDSB is 24.
• In the
Number of Channel
column, the number of channels are automatically updated based on the PDC
type.
• In the
Channel Number
column, the channel number is automatically updated based on the number of
channels configured for the selected module.
For example, if the number of channels configured for a module is 4, then this column lists the channel
numbers as 0, 1, 2, and 3.
• In the
Channel Type
column, the channel type is automatically set based on the PDC type.
• In the
Channel Data Type
column, the channel data type is automatically set based on the PDC type.
• With R410, you can modify the values of the following parameters even after a PDC is associated and
connected to a PIOMB. However, you must ensure that you reload both the DSB and the PIOMB after
modifying the parameter value. If you do not reload both the DSB and the PIOMB, there may be a break in
the connection between the DSB and the PIOMB.
– Channel Description (CHDESCRIPTION)
– Channel Low Range (CHLOWRANGE)
– Channel High Range (CHHIGHRANGE)
7 DEVICE SUPPORT BLOCK (DSB)
161
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...