![Honeywell Experion PKS User Manual Download Page 196](http://html.mh-extra.com/html/honeywell/experion-pks/experion-pks_user-manual_149113196.webp)
Once the PDCNAMEREF is selected the following parameters are updated automatically.
• Slave Name (SLAVENAME)
• Slave Address (SLAVEADDRESS)
• Slot Type (SLOTTYPE)
• PDC Description (PDCDESCRIPTION)
• PDC Number
• Number of Channels (NUMCHANS)
• Channel Number Offset (CHANNUMOFFSET)
• PDC Grouped (GROUPEDPDC)
Attention
The NUMCHANS and CHANNUMOFFSET parameters are updated based on the type of associated
PDCNAMEREF.
If the selected PDC is an input PDC, then the NUMCHANS parameter is set as 2 and the CHANNUMOFFSET is
set as 0.
If the selected PDC is an output PDC, then the NUMCHANS parameter is set as 6 and the CHANNUMOFFSET
is set as 2.
8
Type the physical slot number of the PBHIOMB in the
Slot Number (SLOTNUM)
box.
You must type the correct slot number since the number of channels is displayed based on the slot number.
9
In the
HART Configuration
tab, perform the following steps.
a
Type the process data index in the
Directory Process Data Index (DIRPROCDATAINDEX)
box.
Note
Directory Process Data Index (DIRPROCDATAINDEX)
value must be taken from the device manual.
See the specific device manuals for the data. The
DIRPROCDATAINDEX
value can also obtained from
the GSD file
b
Select the check boxes for the respective HART Enabled channels.
The channel name is automatically displayed in the
Channel Name (CHNLNAME)
column.
Note
The
Channel Name (CHNLNAME)
can be edited only in the Project view.
10
Click
OK
.
The HART Enabled channels appear under the PBHIOMB block in the Project view.
8.4.1 Configuring a PBHCHANNEL block
Prerequisites
• DSB for the PROFIBUS slave module is created and configured.
– HART-enabled modules must be configured in the DSB.
• HART Device Description (DD)-based template is already created in the Library.
• PBHCHANNEL block is created under the PBHIOMB block.
To configure a PBHCHANNEL block
1
From the Project view, double-click the PBHCHANNEL block.
The PBHCHANNEL configuration form appears.
2
In the
Main
tab, perform the following steps.
a
Select the device template from the
Configured AI HART Device (HCFGDEVAI)
or
Configured AO
HART Device (HCFGDEVAO)
list.
The respective DD file is associated to the PBHCHANNEL.
8 PROFIBUS HART INPUT/OUTPUT MODULE (PBHIOM) FUNCTION BLOCK
196
www.honeywell.com
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...