• You must define the channel data type if you have used the configurable input/output PDCs.
10
In the
Channel Data offset
column, select the channel data offset of the digital input/output channel.
11
In the
Bit offset
column, select the bit offset of the digital input/output channel.
• If you have used the fixed PDC types, the bit offsets are displayed automatically.
• You must define the bit offsets if you have used the configurable input/output PDCs.
12
In the
Low Range
column, type the lowest raw value that the channel supports. This parameter is applicable
only for the analog input/output PDCs. For digital input/output PDCs, this parameter is non-editable.
Attention
The channel low range must be less than the channel high range. If channel low range is greater than or equal to
channel high range, the error message "RangeorLimitCrossover" appears during the load of the DSB block. In
addition, the PDC will go into the "Config Load Fail" state, and the DSB will go into the "Configuration Error"
state.
13
In the
High Range
column, type the highest raw value that the channel supports. This parameter is
applicable only for the analog input/output PDCs. For digital input/output PDCs, this parameter is non-
editable.
Attention
To prevent the process data values from being scaled, you can set the channel high and low range as "NaN." When
this is performed, the process value is limited by the values supported by the data type. If PVLO and PVHI ranges
are set to NaN then RAW float of the ranges can be read for the PDC.
14
In the
Init Value
column, define values for each output channel from which the channels must initialize after
recovering from a network down condition. You can define the following values as initial values.
• 0 - 100
For AO channels, numeric initialization value defines percentage value of the output.
For DO channels, initialization value 0 defines OFF state of the channel and value 1 defines ON state of
the channel.
• NaN - If the initialization value is defined as NaN, the output channels (AO and DO) hold the last output
value.
• 0 - If the initialization value is defined as 0, the AO channel initializes to 0 and the DO channel is cleared
to 0 during all error scenarios. However, for the AO channel, if you enter a small non-zero value like
0.001, the channel value initializes to the low range defined for the channel.
For more information, refer to the section “About initialization of AO/DO channels from user-defined
values” on page 152.
15
Click
OK
.
Attention
•
You can view the PDC State, Data Module Number, Data Size, Channel Status, Ch data Boolean, Numeric raw
data, Floating point value values in the Monitoring view after the DSB is loaded.
•
You can set the analog channel output value (Numeric raw data/Floating point value) or the digital channel
output value (Ch data Boolean) from the Monitoring view if you have not associated a PDC to a PIOMB.
7.16.1 Generic DSB specific PDC configuration guidelines
The following list summarizes the Generic DSB specific PDC configuration guidelines that you must remember
while configuring the Generic DSB PDC.
• The number of PDCs supported by GENDSB is 16 and GENIODSB is 64.
• In the
Number of Channels
column, you must enter the number of channels manually.
• In the
Channel Number
column, you must enter the channel numbers in increasing order. If not, this may
result in an unknown channel status behavior.
7 DEVICE SUPPORT BLOCK (DSB)
157
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...