2 PROFIBUS Gateway Module (PGM) Overview
The PROFIBUS Gateway Module is an interface module that can be used with C300 Controller to connect and
communicate with the Profibus devices. The PGM is developed in the Series C form factor for use with the
C300 Controller. The PGM module is an FTE resident module.
As a PROFIBUS gateway, PGM is always a master and communicates with the PROFIBUS compatible slave
devices.
The PGM supports the following functions.
• Redundancy
• Experion events and alarms
• Experion Bulk Build utility
• Experion import/export functionality
• Qualification and Version Control
• Peer-to-peer communications
Attention
The PGM does not retain RAM across power failure using a battery backed RAM. However, it does retain its
configuration in Flash and can resume normal operation upon power up.
PROFIBUS Communication Profiles
The following information is extracted from the PROFIBUS Technical Description describing the PROFIBUS
DP communication profile as defined by the PROFIBUS Standard Definition (EN 50170):
PROFIBUS DP - Decentralized Periphery (DP) is the most frequently used PROFIBUS communication profile.
It is optimized for speed, efficiency and low connection costs and is designed especially for communication
between automation systems and distributed peripherals.
PROFIBUS DP Overview
PROFIBUS DP is a master/slave, token passing network, which utilizes a request/response protocol. Basic data
exchange operations ensure that on a periodic basis, the master sends an output message to each slave device,
which responds in turn with an input message. PROFIBUS DP is typically used as an I/O network. As
compared to a traditional I/O network architecture that requires dedicated wiring between each I/O module and
the controller device, PROFIBUS offers the advantage of a single network/bus on which all I/O peripheral
devices reside.
PROFIBUS PA Overview
PROFIBUS-PA is one of three PROFIBUS variants that are compatible with each other. PROFIBUS PA is
available for applications in process automation with a demand for bus power and intrinsically safe devices.
PROFIBUS PA is linked to the DP network with a coupler module. PROFIBUS PA supports the tree or line
structures and any combination of these two network topologies.
Related topics
“Overview of PGM components” on page 13
11
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...