S E C T I O N 5
Menu Mode Programming
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
About Zone Programming (
∗∗∗∗
56 and
∗∗∗∗
58 Menu Modes)
✱
56 Zone Programming is used to program zones, zone types, report codes, enroll 5800 RF Wireless
Transmitter serial numbers, and identify the type of loop input device(s). This mode can also be used
to enter alpha descriptors for programmed zones; however, we recommend entering descriptors in
menu mode
✱
82 (
Alpha Descriptor Programming
after all zone programming has been completed).
For a faster method of zone programming, you can use the
✱
58 Expert Programming Mode instead of
✱
56 Zone programming. The
✱
58 Expert Programming Mode is designed for those who have had
previous experience in programming control panels of this type.
NOTE:
Alpha display prompts are shown in a double-line box.
∗∗∗∗
56 Zone Programming Procedure
Zone Programming involves:
1. Entering the zone number to be programmed;
2. Making appropriate entries at the prompts;
3. Confirming the serial number of wireless transmitter zones.
Start Zone Programming mode by pressin
g
✱
56 while in Data Programming mode. The following
prompts are displayed:
PROMPT
VALID ENTRIES
EXPLANATION
SET
TO CONFIRM?
0 = NO 1 = YES
Set to Confirm
0 = no
1 = yes
If 1 (Yes) is entered, the XMIT TO CONFIRM prompt appears later
in this procedure after entering RF transmitter serial and loop
numbers, and lets you confirm the programming of each RF
transmitter.
We recommend that you confirm every
transmitter.
If 0 (No) is entered, the XMIT TO CONFIRM prompt is automatically
skipped.
This option is ignored if programming wired zones only.
Enter Zn Num.
(00 = Quit)
10
Zone Number
wired zones 01-48
wireless zones 09-48
RF button zones 49-64
91 = addr. device report enable
92 = duress report enable
95, 96, 99 =emergency zones
00 to quit
[
∗
] to continue
Enter the zone number that you wish to program. Zone 10 has been
entered as an example in the display at left.
Enter a report code for zone 91 to enable addressable device
reporting.
Enter a report code for zone 92 to enable duress reporting.
95, 96, 99 are emergency (panic) key zones.
Zn ZT P RC In: L
10 00 1 10 RF: 1
OR
Zn ZT P RC In: AD
10 00 1 10 AW: 07
OR
Zn ZT P RC HW: RT
10 00 1 10 EL 1
Summary Screen
[
∗
] to continue
A summary display appears.
“IN: L” appears for wireless zones and indicates input type and loop.
“IN: AD” appears for wired expansion zones (AW) and indicates the
module’s address (AD), which is based on the zone number.
“HW: RT” appears for basic wired zones and indicates configuration
(EOL, NO, NC, zone doubling, double-balanced) and response time
selection.
5-1