- -
HLP-C
+
Inverters
C083), the inverter will turn into self-protection, display the
fault signal and stop output.
The related parameters see C083
.
C085 Rated Motor Voltage
It is set according to the rated voltage value of the namplate. For
230V class inverters the default is 220, while for 400 V class
inverters the default is 380V.
C086 Rated Motor Current
It is set according to the rated value of the namplate. This
parameter can be used to restrict output current of the inverter to
prevent overcurrent and protect the motor. If the current of the
motor has exceeded this value the inverter of AC motor will turn
into self-protection.
C087 Motor Poles
Set Range
:
02~60
Factory Setting
:
04
This parameter is set for the pole number of the motor according
to the namplate of the motor.
C088 Rated Motor Revolution
Set Range
:
0~9999
Factory Setting
:
1440
This should be set according to the actual revolution of the
motor. The displayed value is the same as this parameter. It can
be used as monitoring parameter, which is convenient to the
user. This parameter set value corresponds to the revolution
speed at 50Hz.
C089 Motor No-load Current
Set Range
:
0~100
Factory Setting
:
40
The setting of Motor no-load current will affect the quantity
of slip compensation. 100% current is the rated current of the
motor.