HLP-C
+
Inverters
C060 Up-down Mode
Set Range
:
0~1
Unit
:
1
Factory Setting
:
0
0
:
Not memorized
1
:
Memorized
Through the setting of this parameter whether the value changed
by UP-DOWN will be memorized after stopping can be selected.
When C060 is set to 1, if restarting after stopping, the value at
stopping will be memorized. If restarting after power off, the
values at power off will not be memorized, but the value set by
C000 will be memorized. When C060 is set to 0, if restarting
after stopping, it will return to the value of C000, the value
changed by up-down will not be memorized..
C062 Timer 1 Time
Set Range
:
0.0~10.0
Unit
:
1
Factory Setting
:
0
C063 Timer 2 Time
Set Range
:
0~100
Unit
:
1
Factory Setting
:
0
Timer 1 is a timer of 0~10.0S and Timer 2 is a timer of 0~100S.
When the timer for multi-input terminal is opened or closed
the timer starts to count time. When the set time is reached the
corresponding multi-output contact will act. When the timer
cut off open the timer for multi-output will reach to reset time.
During running, if the machine stops due to fault, the timer will
count time normally and not suspend; if the machine stops due
to power off, the timer will reset automatically.
he counter can be regarded as the trigger by many function
outside end sons, when counter value reaches establishing value
C064, corresponding many function output contact movement,
after putting by counter, counter put the location, count and
resume, touching off the signal can be utilized and close to the
switch , photoelectric switch ,etc..