HLP-C
+
Inverters
C070 Uniform Frequency 1 Set
C071 Uniform Frequency 2 Set
Set Range
:
0.00~600
Unit
:
0.1Hz Factory Setting
:
0.0
When the output frequency reaches the set values of C070, C071
the corresponding multi-function output contact will act.
C072 Analog Quantity Select
Set Range
:
0~4
Factory Setting
:
0
0
:
0~10V 1
:
0~5V
2
:
0~20mA
3:4~20mA 4:0~10V and 4~20mA stacked
This parameter can be set to satisfy different analog input
signals.
When C072=4, output frequency =
(
U/Umax + I/Imax
)
*50Hz/2
Among which: U
:
Analog Quantity Voltage Quantity; Umax:
Maximum Analog Quantity Voltage Quantity; I: Analog
Quantity Current Quantity; Imax: Maximum Analog Quantity
Current Quantity.
For example, When +10V and 20mA are repectively entered for
the analog quantity, the output frequency of the inverter is 50Hz.
(In case the max. operation frequency is set to 50Hz)
C073 Analog Quantity Low End Frequency
Set Range
:
0.0~600.0Hz
Unit
:
0.1Hz Factory Setting
:
0.0
074 Bias Direction of Low End Frequency
Set Range
:
0~1
Factory Setting
:
0
0
:
Forward dirction
1
:
Reverse direction
C075 Analog Quantity High End Frequency
Set Range
:
0.0~600.0Hz
Unit
:
0.1Hz Factory Setting
:
51.0
C076 Bias Direction of High End Frequency
Set Range
:
0~1
Factory Setting
:
0
0
:
Forward dirction
1
:
Reverse direction