HLP-C
+
Inverters
0:STOP is invalid.
1:STOP is valid.
This parameter set is only valid when C012 is set as l or 2.
When the control method is set for external terminals or
communications, the STOP key on the panel can be chosen to be
valid or not. When choosing it as valid, the STOP key can stop
the inverter in running. When it needs restarting, the former
running signal should be released first and then restarting is
allowable.
C018 S-Curve Time
Set Range:0~6500S
Unit:1
Factory Setting:0
This parameter can be set for no impact slow start or slow stop
of the inverter when starting or stopping. When starting S-curve
the inverter will make accel or decel curve of different speed
rates according to Accel/Decel Time.
When C018 is set to 0, S-curve is invalid, i.e. accelorate or
decelorate in straight line. Without consideration of stall the
actual Accel/Decel Time is equal to the set Acel/Decel Time
plus S-curve Time.
C019 Carrier frequency (Note:0 ~ 15 corresponding to 0 ~ 16K Hz)
Set Range:0~15
Unit:01
Factory Setting:09
The carrier frequency has some affect on the electromagnetic
noise of the motor, and meanwhile the level of the carrier
frequency has certain relation with the heating capacity of the
inverter and the interference to the environment.
See the following table:
Carrier
Frequency
Electromagnetic
Noise
Heating
Capacity
Interference
to the
Environment
Low
↓
High
High
↓
Low
Small
↓
Large
Little
↓
Great