HLP-C
+
Inverters
CN1 State
1 2 3
1 2 3
Potentiometers of the panel
Analog quantities of external
terminals
2
:
Set by the communication ports.
The running frequency is given through the serial communication
ports.
C014 Starting Mode Select
Set Range
:
0~1
Unit
:
1
Factory Setting
:
0
Two starting modes are available for different equipment.
0
:
Start from the starting frequency.
When C092 is set as 0, i.e. DC brake is invalid when starting, it
starts running from its starting frequency. When C092 is set to
any non zero value, i.e. DC brake is valid when starting, it will
first have a DC braking when starting, and then start from the
starting frequency.
Related parameters refer to C091 and C092.
1
:
Starting by Speed Search
This function can be used in the restarting of large inertia load.
When restarting, the inverter will trace the former speed from
the set frequency downward. In case of large inertia equipment,
when restarting, it can implement the running command right
away withourt waiting for the complete stop of the equipment by
tracking the former frequency to save time.
Note: When the inverter is restarted by speed search, it will
start tracking the frequency from its set frequency downward,
and search it at the highest speed. When starting, the current
will be high, and over current or stall may occur. Be sure to
pay attention to the adjustment of current standard position
of speed search. Generally, C095 should be set around 100%.
The concrete value should be specifically set according to the
characteristics of mechanical load.