C102 PID Constant P
Set Range
:
0.0~1000%
Unit
:
1
Factory Setting
:
100
This proportional constant is set for the error value gain. If I=0,
D=0,it is only for proportional control.
C103 PID Constant I
Set Range
:
0.1~3600
Unit
:
1
Factory Setting
:
5.0
The integral time (I) is set for the reaction speed for PID. The
larger the I value is the slower the reaction speed is. But if the
integral time value is set too small, it will cause vibration.
C104 PID Constant D
Set Range
:
0.01~10.0
Unit
:
0.01
Factory Setting
:
0
This didderential time (D) is set for the depression operation of
PID. The larger the D value is, the more obvious the depression
operation is. When D is set to 0, it means this function invalid.
C105 PID Constant Target Value
Set Range
:
0.0~100.0
Unit
:
0.1
Factory Setting
:
0.0
This target value can be set through external voltage signal or
the digital operator.100% target value is corresponding to the
frequency quantity at +10V.
PID closed-loop control is usually used in the process control
of no fast physical quantity changes, such as pressure control,
temperature control, etc. The feedback signal is usually taken