23
03.03
Proportional gain P
The speed of PID adjustment is set by two parameters: proportional
gain and integration time. For fast adjustment, it is necessary to
increase proportional gain and reduce integration time; for slow
adjustment, it is necessary to reduce proportional gain and increase
integration time.
Generally, differential time is no necessary to set
0.01
~
5.00
2.00
○
03.04
Integration time Ti
0.1
~
50.0s
1.0s
○
03.05
Derivative time Td
0.1
~
10.0s
0.0s
○
03.06
Sampling period T
The larger the sampling period, the slower the response, but the
better the interference signal suppression effect, so it is generally
unnecessary to set it.
0.1
~
10.0s
0.0s
○
03.07
Deviation limit
The deviation limit is the ratio of the absolute value of the deviation
between the feedback amount and the given amount of the system.
When the feedback amount is within the deviation limit, the PID
adjustment will not act.
0.0
~
20.0%
0.0%
○
03.08
Closed loop preset
frequency
Frequency and running time of inverter before PID is put into
operation
0.0
~
upper limit
frequency
0.0Hz
○
03.09
Preset
frequency
holding time
0.0
~
999.9s
0.0s
×
03.10
Sleep
threshold
coefficient
If the actual feedback value is greater than the set value, and the
frequency output by the frequency inverter reaches the lower limit
frequency, the frequency inverter will enter the sleep state after the
delay waiting time defined in 03.12 (i.e., running at zero speed); The
value is a percentage of the PID set value.
0.0
~
150.0%
100.0%
○
03.11
Awakening threshold
coefficient
If the actual feedback value is less than the set value, the frequency
inverter will get out of sleep and start working after the delay waiting
time defined in 03.13; The value is a percentage of the PID set value.
0.0
~
150.0%
90.0%
○
03.12
Sleep delay time
Set up Sleep delay time
0.0
~
999.9s
100.0s
○
03.13
Wake delay time
Set up Wake delay time
0.0
~
999.9s
1.0s
○
03.14
Deviation
between
feedback and set
pressure
when
entering sleep
This function parameter is only valid for disturbance sleep mode
0.0
~
10.0%
0.5%
○
03.15
Delay time of burst
detection
Set the burst tube detection delay time
0.0
~
130.0s
0.0S
○
03.16
High pressure
detection threshold
When the feedback pressure is greater than or equal to this set value,
the explosion failure “EPA0” will be reported after the explosion delay
at 03.15, and when the feedback pressure is less than this set value,
the explosion failure “EPA0” will automatically reset; The threshold is
a percentage of the given pressure.
0.0
~
200.0%
150.0%
○
03.17
Low pressure
detection threshold
When the feedback pressure is less than this set value, the explosion
failure “EPA0” will be reported after the explosion delay at 03.15, and
when the feedback pressure is greater than or equal to this set value,
the explosion failure “EPA0” will automatically reset; The threshold is
a percentage of the given pressure.
0.0
~
200.0%
50.0%
○
03.18
Measurement range
of sensors
Set the maximum range of the sensor
0.00
~
99.99
(MPa
、
Kg)
10.00MPa
○
04 group -advanced functions parameters
Function
code
Name
Setting range
Minimum unit
Factory
setting
Change
04.00
Motor rated voltage
Setting of motor parameters
0
~
500V
:
380V
0
~
250V
:
220V
Model
setting
×
04.01
Motor rated current
0.1
~
999.9A
Model
setting
×
04.02
Motor rated speed
0
~
9999RPM
Model
setting
×
04.03
Motor rated frequency
1.0
~
999.9Hz
50.0Hz
×
04.04
Motor stator resistance
Set the motor stator resistance
0.001
~
20.000Ω
Model
setting
○
04.05
Motor no-load current
Set the motor no-load current
0.1
~【
04.01
】
Model
setting
×