11
the maximum frequency.
Its range is-100.00%
~
100.00%.
Communication control
command
2002H
0001H: external fault input
W
0002H: fault reset
Read the
stop
parameter
description of running /
2102H
Set the frequency (two decimal places)
R
2103H
Output frequency (two decimal places)
R
2104H
Output current (one decimal place)
R
2105H
Bus voltage (one decimal place)
R
2106H
Output voltage (one decimal place)
R
2107H
Analog input AI (two decimal places)
R
2108H
Reserved
R
2109H
Current count value
R
210AH
Revolving speed of motor
R
210BH
Analog output AO (two decimal places)
R
210CH
Reserved
R
210DH
Inverter temperature (one decimal place)
R
210EH
PID feedback value (two decimal places)
R
210FH
PID set value (two decimal places)
R
2110H
Reserved
R
2111H
Pulse frequency input
R
2112H
Current fault
R
2113H
Current timing value
R
2114H
Input terminal status
R
2115H
Output terminal status
R
2116H
BIT0: Run/Stop
BIT1: Forward/reverse rotation
BIT2: JOG
BIT3: DC braking
BIT4: Reserved
BIT5: Overvoltage limit
BIT6: Constant speed frequency reduction
BIT7: Overcurrent limit
Bit8~9: 00-Zero speed /01- Acceleration /10- Deceleration
/11- Uniform speed
BIT10: Overload Pre-alarm
Bit12~13 Run command channel: 00- Panel /01- Terminal
/10- Communication
Bit14~15 bus voltage status: 00- normal /01- low voltage
protection /10- overvoltage protection
R