42
LED bit: Stage 5 acceleration and deceleration time
0
~
1
LED ten bits
:
Stage 6 acceleration and deceleration time
0
~
1
LED hundred bits:Stage 7 acceleration and deceleration time
0
~
1
LED thousand bits
:
Reserved
01.33
Acceleration time 2
0.1
~
999.9 s
10.0
01.34
Deceleration time 2
0.1
~
999.9 s
10.0
Two groups of acceleration/deceleration time can be defined, and the acceleration/deceleration time 1
~
2 during inverter operation can be selected through
different combinations of control terminals. Please refer to the definition of acceleration/deceleration time terminal function in 02.13
~
02.17.
01.35
Time unit selection
000
~
211
000
LED bit: process PID time unit
LED ten bits: simple PLC time unit
LED hundred bits: regular acceleration and deceleration time unit
LED thousand bits: reserved
0: 1 second
1: 1 minute
2: 0.1 second
This function code defines the dimension of acceleration and deceleration time.
01.36
Forward and reverse dead time
0.0
~
999.9s
0.0
The waiting time for the inverter to transition from forward running to reverse running, or from reverse running to forward running, is t1 as shown in the figure below.
Figure 01-9 Schematic diagram of forward and reverse dead time
Group 02-analog and digital input and output parameters
02.00
AI input lower limit Voltage
0.00V/0.00mA
~【
02.01
】
0.00