59
05.14
Amplitude suppression coefficient
0
~
12
5
05.15
The Lower limit frequency of oscillation suppression
0.0
~【
05.16
】
5.0Hz
05.16
The upper limit frequency of oscillation suppression
【
05.15
】~【
00.05
】
45.0Hz
In case of motor oscillation, it is necessary to set the effective value of 05.00 thousand bits, turn on the oscillation suppression function, and then adjust it by
setting the oscillation suppression coefficient. In general, the oscillation amplitude is large, so it is unnecessary to set the oscillation suppression coefficient of 05.13,
05.14
~
05.16; In case of special occasions, they should be used together from 05.13
~
05.16.
05.17
Selection of wave-by-wave current limit
000
~
111
011
LED bit
:
In acceleration
0
:
invalid
1
:
valid
LED ten bits
:
In deceleration
0
:
invalid
1
:
valid
LED hundred-bits: In constant speed
0
:
invalid
1
:
valid
LED Thousand bits:Reserved
05.18
Output phase lost protection detection coefficient
0.00
~
20.00
2.00
When the ratio of the maximum value to the minimum value in the three-phase output current is greater than this coefficient and the duration exceeds 6 seconds,
the frequency inverter reports the output current imbalance fault EPLI
;
; Output open-phase protection is invalid when 05.18=0.00.
05.19
Frequency drop coefficient of instantaneous power failure
0
:
the instantaneous stop function is invalid
1
~
9999
0
05.20
Instantaneous power down loss frequency reduction voltage point
220V:180
~
330V
250V
380V:300
~
550V
450V
Model setting
If the inverter bus voltage drops below 05.20* rated bus voltage, and the instantaneous stop control is valid, the instantaneous stop starts to act.
06 group: communication parameters
06.00
Local Address
0
~
247
1