40
Fig. 01-7 PLC start mode 1
2: Start from the stage and frequency of shutdown (failure) time
In case of shutdown during operation (caused by shutdown command, fault or power failure), the inverter not only automatically records the running time at the
current stage but also records the running frequency at the shutdown time, and then recovers to the running frequency at the shutdown time after starting again, and
the remaining phases of the frequency run, as shown in the following figure:
Fig. 01-8 PLC start mode 2
Thousands of LEDs: power-down storage options
0: do not store
The PLC running state is not memorized when the power is off, and it starts to run from the first stage after power-on.
1: storage
The PLC running status is memorized when the power is off, including the stage at the time of power down, the running frequency, and the running time. Restart
after power-on, it will automatically enter this stage, and continue to run for the remaining time at the frequency defined in this stage.
01.17
Multi-speed frequency 1
-Upper limit frequency ~ +upper limit frequency
5.0
01.18
Multi-speed frequency2
-Upper limit frequency ~ +upper limit frequency
10.0