62
07.03
Timing setting
0
~
9999s
0
Set the timing time
07.08
Swing frequency control
0
~
1
0
0: prohibited
1: valid
07.09
Swing frequency control
0
~
1
0
0: fixed swing
The reference value of swing is the maximum output frequency (00.04).
1: variable swing
The reference value of the swing is the given channel frequency.
07.10
Swing frequency stop starting mode selection
0
~
1
0
0: start according to the state memorized before stop
1: restart starting
07.11
Swing frequency amplitude
0.0
~
100.0
%
0.0%
The swing frequency amplitude is determined by 07.09. If 07.09=0, then the swing amplitude
AW = Maximum output frequency*07.11
If 07.09=1, then the swing
AW=given channel frequency*07.11.
07.12
Jump frequency
0.0
~
50.0
%
0.0%
This function code refers to the amplitude of the rapid decrease when the frequency reaches the upper limit frequency of the traverse frequency during the swing
frequency process. Of course, it also refers to the amplitude of the rapid increase after the frequency reaches the lower limit frequency of the traverse frequency. This
value is relative to the percentage of wobble frequency amplitude (07.11).
If set to 0.0%, there is no sudden jump frequency.
07.13
Swing frequency rise time
0.1
~
3600.0s
5.0
07.14
Pendulum frequency falling time
0.1
~
3600.0s
5.0
07.15
Frequency delay of swing frequency upper limit
0.1
~
3600.0s
5.0
07.16
Frequency delay of swing frequency lower limit
0.1
~
3600.0s
5.0