background image

 

Chimney Draft Requirements: 

 Chimney draft is the measurement of the pull or vacuum created 

by the chimney. It can be measured with a manometer and is expressed in inches of water (inch 
wc). To measure you need to drill a small hole in the stovepipe between the flue collar and any  
 
 
stovepipe dampers installed into the stovepipe system. Insert the manometer connection into the 
hole and note the reading. Ideally you should have a reading of between -.03 and -.06 inches of 
water (inch wc). If the chimney produces less than -.03 your fire can be very sluggish. In worst 
case instances combustion byproducts like smoke and carbon monoxide can be expelled from the 
furnace. This can possibly create a very dangerous situation.     
   A draft of more than -.06 (inch wc) will waste some of your heat by causing it to be drawn up the 
chimney too quickly. The higher the draft goes the more heat that is wasted up the chimney. A 
very strong overdraft can also cause the stove to over fire. Over firing can cause the stove to 
develop extremely high temperatures resulting in possible damage to the stove or a fire. Draft 
should never exceed -.08 (inch wc). Over drafting can be controlled by installing a damper in the 
stovepipe. This damper can be a barometric or manual damper. It is recommended to have this 
damper installed during the stove installation. The damper may be installed in the vertical or 
horizontal portion of the stovepipe. The stovepipe damper must be installed and calibrated 
according to the damper manufacturer’s instructions.   
 

   CAUTION: BE SURE TO FOLLOW ALL LOCAL CODES AND SAFETY 
REQUIREMENTS WHEN INSTALLING THE STOVE. 

 

 

CAUTION: THE USES OF ALUMINUM TYPE B GAS VENT FOR SOLID FUEL 
VENTING IS UNSAFE AND PROHIBITED BY THE NATIONAL FIRE PROTECTION 
ASSOCIATION CODE 

 

III. Location of Furnace and Installation

   

 

 

 
 

 

WARNING:   THE INSTALLATION OF THESE STOVES MUST COMPLY WITH 
STATE AND LOCAL REQUIREMENTS AND BE INSPECTED BY THE STATE OR 
LOCAL INSPECTOR IF REQUIRED.  NOTE:  THESE STOVES ARE NOT 
APPROVED OR RECOMMENDED FOR USE IN MOBILE HOMES. 

 
The location of the stove is very important for optimum stove performance as well as safety 
assurance.  When searching for the location of the stove be sure to strictly follow manufacture

r’s 

guidelines, clearance to combustible material requirements, local building, and fire codes.  Failure 
to follow manufacturer

’s instruction and local jurisdiction codes may result in bodily injury, property 

damage, fire, or death.  Locate the stove where there is sufficient air supply for proper operation to 
occur. It is vitally important to locate the stove next to existing forced air furnace as well as next to 
the chimney.  The closer placement to these two items the better the stove will perform, and 
achieve maximum heat flow.  The longer the chimney connector pipe (stovepipe) and farther away 
the stove is from the chimney the less performance is achieved from the stove.   
Please consider the construction and layout of the home to be heated and make placement of the 
stove to achieve maximum heat benefit produced by the stove. 

 

 
Connection of stove to the chimney should be made as directly as possible and not more than two 
bends when needed should be used.  No reduction in flue pipe below 7 inches diameter heater 
outlet should be used.  The pipe connecting the stove to the chimney should be at least 24 gauge. 
Slope the flue pipe back towards the heater 1/4 inch per foot of horizontal run, so that any 
condensation forming in the pipe will be carried back into the heater.  The connector pipe should 

Summary of Contents for 55 FA

Page 1: ...DAMAGE PERSONAL INJURY OR DEATH FURNACE SURFACES MAY BECOME HOT WHILE IN OPERATION HIGH FURNACE TEMPERATURES MAY IGNITE CLOTHING OR FLAMMABLE MATERIAL FOR USE OF SOLID FUEL COAL ONLY OTHER FUEL SOURC...

Page 2: ...FM output of each furnace You can then get an idea if the ductwork is sized such that the operating static pressure of the two combined will not go over the maximum for either if both operate at the s...

Page 3: ...d by a chimney professional The structural foundation of the chimney and liner is important If existing clay liner is cracked or damaged it is recommended to re line the chimney with a stainless steel...

Page 4: ...urnace should be a minimum of 7 inches in diameter Flue Size Continued The flue size also has a maximum size of inches in order to sustain the desired draft For an interior chimney the flue and chimne...

Page 5: ...FOR SOLID FUEL VENTING IS UNSAFE AND PROHIBITED BY THE NATIONAL FIRE PROTECTION ASSOCIATION CODE III Location of Furnace and Installation WARNING THE INSTALLATION OF THESE STOVES MUST COMPLY WITH STA...

Page 6: ...ng concealed spaces or enter the chimney in the attic If connection is made through a combustible wall a listed and approved wall thimble pass through must be used following the manufacturer s instruc...

Page 7: ...all or Ceiling 18 Unit must be placed on a noncombustible floor Hot Air Supply Duct Hookup With the furnace now in place and the flue connector connected to the chimney it is time to connect the suppl...

Page 8: ...ill greatly improve the air movement up through the system There are also cover plates along both sides at the bottom of the furnace These can also be removed during a power outage to increase the nat...

Page 9: ...ation formats Note these illustrations reflect typical installations and are for design purposes only Illustrations and diagrams are for informational purposes only These diagrams are not drawn to sca...

Page 10: ......

Page 11: ...to operate other than as intended Do not have hot air from gas or oil furnace flow downward into the Hitzer Furnace and flow out the Hitzer Furnace to existing duct work IV Operation Of Furnace WARNI...

Page 12: ...y load the stove to maximum heating potential Starting An Anthracite Coal Fire Starting an Anthracite coal fire takes time and patience Take several sheets of newspaper crumble into balls and place on...

Page 13: ...t air flow and the ability of the coal to burn When this happens this block of burning coal must be broken up with a poker to restore proper operation Add the coal in a couple of stages however it is...

Page 14: ...However when the stove is turned down and not much heat is needed the thermostat controlling the draft closes The gases now have no oxygen to burn and there is very little air movement through the st...

Page 15: ...EXTREMELY HOT FIRE THE CHIMNEY CONNECTOR AND CHIMNEY SHOULD BE INSPECTED AT LEAST TWICE MONTHLY DURING THE HEATING SEASON TO DETERMINE IF A SOOT BUILD UP HAS OCCURRED IF SOOT HAS ACCUMULATED IT SHOUL...

Page 16: ...till you are ready to use the furnace again in the fall Have the chimney inspected and cleaned if necessary If the optional filter housing is not installed you will need to clean the blower wheel Alwa...

Page 17: ...all be the responsibility of the original purchaser and the said Hitzer Inc shall have the final determination and be the final determiner as to whether or not said component is defective Any labor co...

Page 18: ...order for the above stated limited warranty to be effective and binding upon Hitzer Inc this portion herein must be detached and sent by the original owner to Hitzer Inc to the above stated address wi...

Reviews: